Required Pressure Drop Across the Heater
The thermal  uid pressure drop across your heater is critical. This should be
recorded at the completion of start-up, as follows:
1. The pressure drop value is obtained by subtracting the heater outlet
pressure from the heater inlet pressure when the thermal  uid is at normal
operating temperature.
2. At the recommended standard  ow rates, and .7 sp gr, the pressure drop
cross the heater should be as shown in Table 10.
3. In the event of an abnormal reading, contact Fulton Service immediately.
Failure to take immediate action in the event of reduced  uid ow may
result in rapid and serious degradation of the  uid, with possible damage
to the heater.
TABLE 10  REQUIRED PRESSURE DROP ACROSS THE HEATER
Model Recommended
GPM (schedule 80)
Recommended
GPM (schedule 40)
Pressure Drop PSI
FT-0080-C 44 50 25
FT-0120-C 66 75 27
FT-0160-C 88 100 20
FT-0240-C 132 150 30
FT-0320-C NA 250 25
FT-0400-C 220 250 25
FT-0600-C 330 375 26
FT-0800-C 440 500 26
FT-1000-C 550 615 18
FT-1200-C 660 730 27
FT-1400-C NA 800 27
FT-0400-S NA 400 18
FT-0600-S NA 600 16
FT-0800-S NA 800 19