User guide
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4-5
SECTION 4 FTCS-IOM-2013-1114 MAINTENANCE
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
4 CAUTION
Use extreme caution when using
any cleaning solution. Refer to local
regulations for disposal requirements.
All maintenance procedures should
be completed by trained personnel.
Appropriate training and instructions
are available from the Fulton Service
Department at (315) 298-5121 or your
local Fulton Thermal Representative.
In order to meet warranty conditions,
ensure all appropriate maintenance
activities are performed.
Semi-Annual Maintenance Schedule
1. Pull burner and inspect for heat stress or soot. Clean or replace as
necessary.
2. Inspect pilot tube assembly and ignition electrode. Clean or replace if
necessary. Reset ignition settings to manual speci cations.
3. Inspect internal surfaces of the heater. Inspect refractory for cracks. Cracks
larger than ¼” wide will require repair or replacement of the refractory.
Inspect coil for sooting. If soot is present, it can be removed by utilizing a
brush or compressed air for light sooting. See Soot Cleaning section of
this manual.
4. Have combustion checked for e ciency.
5. Review daily log sheets noting any deviations from the norm.
Annual Maintenance Schedule
1. Replace the ignition electrode(s).
2. If the unit utilizes a ame rod, replace.
3. Clean all strainers in the thermal uid system.
4. Take a one quart sample of thermal uid and return to the thermal uid
manufacturer for analysis.
5. Schedule local Fulton representative or factory service technician to
perform an annual preventative maintenance.
General Maintenance Procedures
Lubrication
Di erent motor manufacturers recommend various intervals for lubrication
schedules. Load variations will dictate the frequency and amount of lubrication
required.
When developing your lubrication schedule, consider the thermal uid
pump and all system pumps.
If you have a thermal uid circulating pump with a packed seal, the
condition of the pump packing should be checked regularly. If uid
leakage increases, tighten the packing ¼ turn daily.