Cut Sheet

(800) 888-5538 sales@functionaldevices.com www.functionaldevices.com
20191117
CLOSED
OPEN
AUTO
Org
Org
Selectable Jumper Wire
5-25 Vac/dc
CONTROL INPUT
10-30 Vac/dc
POWER INPUT
LOW COIL INPUT RELAY
SPECIFICATIONS
Notes:
Normally Open or Normally Closed selected by
yellow jumper wire
Power Input:
Control Input:
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
10-30 Vac/dc, 50-60 Hz
5-25 Vac/dc, 50-60 Hz
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V Rated
UL Listed, UL916, UL864, C-UL
California State Fire Marshal, CE, RoHS
UL Accepted for Use in Plenum, NEMA 1
No
Yes
Contact Ratings:
10 Amp Resistive @ 120-277 Vac
10 Amp Resistive @ 28 Vdc
480 VA Pilot Duty @ 240-277 Vac
480 VA Ballast @ 277 Vac
Not rated for Electronic Ballast
600 Watt Tungsten @ 120 Vac (N/O)
240 Watt Tungsten @ 120 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
Power Input Ratings:
33 mA @ 10 Vac
35 mA @ 12 Vac
46 mA @ 24 Vac
55 mA @ 30 Vac
13 mA @ 10 Vdc
15 mA @ 12 Vdc
18 mA @ 24 Vdc
20 mA @ 30 Vdc
Control Input Ratings:
.4 mA @ 5 Vdc
.9 mA @ 10 Vdc
1 mA @ 12 Vdc
2 mA @ 24 Vdc
3 mA @ 24 Vac
(Non Polarized)
RIBTELS
Enclosed Relay Hi/Low Separation 10 Amp
SPST + Override, 10-30 Vac/dc Power Input
+ 5-25 Vac/dc Control Input

Summary of content (2 pages)