Operating Temperature:
Humidity Range:
Accuracy:
Loading:
Max Sense Voltage:
Approvals:
-30 to 140° F
5 to 95% (noncondensing)
98.8% Full Scale
RIBXGTV10, (0-20 Amp), 5% Error @ 60.4 kΩ
RIBXGTV10, (0-50 Amp), 5% Error @ 25.24 kΩ
RIBXGTV10, (0-100 Amp), 5% Error @ 13.65 kΩ
600 Vac
UL Listed, UL916, UL864, California State Fire
Marshal, C-UL, CE, RoHS
RIBXGTV10
Enclosed Self-Powered Spilt Core Multi-Range (0-20A, 50A, or 100A) AC Transducer
with 0-10Vdc Terminal Output
Removable Mounting Tab
2.520”
1.100”
1.750”
2.000”
Output: Terminal Strip
Accepts 14-22 AWG wire
DIP Switches
2.000”
Wire Clamp
.52” x .52” Opening for
Wire Being Monitored
Mounting/Installation:
Sensor Type:
Removable mounting tab provided.
The wire clamp locks against the wire
being monitored, securing the unit
in place.
Split core with voltage output
DIP SWITCH
1 2 Sensing Range
OFF OFF 0-20 Amp
OFF ON 0-50 Amp
ON OFF 0-100 Amp
SPECIFICATIONS