Submittal Sheet

I²t, max. 1A²·s
Built-in incoming fuse T 3,15 A/250 V (not accessible)
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 6 A characteristic C
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24V
Total tolerance, static ± 3%
Static mains compensation, approx. 0.1%
Static load balancing, approx. 1%
Residual ripple peak-peak, max. 150mV
Residual ripple peak-peak, typ. 30mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 140mV
Adjustment range 22.8...28V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior Overshoot of Vout < 3 %
Startup delay, max. 0.3s
Voltage rise, typ. 15ms
Rated current value Iout rated 5A
Current range 0...6A
● Note
6 A up to +45°C; +60 ... +70 °C: Derating 1.6%/K
Supplied active power typical 144W
Short-term overload current
● on short-circuiting during the start-up typical
18A
● at short-circuit during operation typical
18A
Duration of overloading capability for excess current
● on short-circuiting during the start-up
800ms
● at short-circuit during operation
800ms
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 88%
Power loss at Vout rated, Iout rated, approx. 16W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.3%
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
3%
6EP1333-2BA20 Subject to change without notice
Page 2/
4
07/30/2018 © Copyright Siemens