User's Manual

36
REG21: Serial Interface Setting 2 [default value: 09H]
Bits 7 – 4: Reserved
The FDL01TU does not use this register. Keep the default value as it is.
Bit 4: Command Header
0
Use REG 10 character
1
Use Break signal
Table 5–16: Command Header
Bit 1: Flow Control
0
Software flow control (default value)
1
Hardware flow control
Table 5–18 Software/Hardware Flow Control Settings
Selects the flow control method. This setting must match the connected terminal
equipment’s setting.
Hardware flow control uses the two control lines RTS and CTS. When using with
the RS485 interface, be sure to set to 0.
Software flow control uses XON and XOFF codes.
Bit 0: Flow Control 2
0
disable flow control
1
enable flow control
Table 5–31: Flow Control 2 Settings
Enable or disable flow control between the terminal and FDL01TU modem connected
through the RS-232C serial interface.
This function should normally be enabled, otherwise buffer overflow can occur and
data may be lost.
REG22: Serial Interface Setting 3 [default value: 00H]
Bit 7: Enable and Disable Reception
0
Enable reception at the initial state (default value)
1
Disable reception at the initial state
Table 5–19: Enable/Disable Reception
The initial state is in reception enable. Depending on an usage of the modem, the
initial state of the modem may be better in the reception disable state. In such a case,
use this setting.