Instructions / Assembly

For a copy of the warranty, contact your local
distributor or visit our website at www.gaf.com
40 YEAR LIMITED WARRANTY
RIDGE VENTS CLASS A CLASSIFIED BY
UNDERWRITERS LABORATORIES INC.
®
AS TO AN
EXTERNAL FIRE EXPOSURE WHEN INSTALLED IN
ACCORDANCE WITH INSTRUCTIONS PROVIDED
WITH RIDGE VENTS 9M61
File R15072
Made from over
90% recycled fiber;
over 30% post-consumer content.
IMPORTANT: Proper
attic ventilation reduces
moisture build-up
and can prevent
mold growth.
Instructions for
Nail Gun Installation
Cobra
®
ExhaustVent
Application Instructions
NOTE:
Calculations for a Balanced Ventilation System...
To achieve a “balanced system” with COBRA
®
EXHAUST VENT, there must be an air intake system (i.e. soffits or
undereave vents). For proper ventilation, the amount of undereave ventilation must equal the amount of ventilation at
the ridge. NO
TE: In no case should the amount of exhaust ventilation exceed the amount of intake ventilation.
To determine the minimum square feet of net free ventilation area (NFVA) needed for a balanced ventilation system,
use the following formula:
Sq. ft. of attic floor space = Min Sq. ft. of NFVA needed
300
• COBRA
®
EXHAUST VENT has 16.9 (hand nail) and 14.1 (nail gun) square inches of NFVA per lineal foot.
To determine how many feet of Cobra Ridge Vent is needed, use the following formula:
1/2 x (Min. Sq. ft. of NFVA needed) x 144/16.9 or 14.1 = Min. lineal feet of ridge vent needed
To determine the amount of undereave vent required, use the following formula:
X = NFVA (Sq. In. per. lin. ft.) of the undereave vent or intake vent system selected
1/2 x (Min. Sq. Ft. of NFVA needed) x 144/X = Min. lineal feet of undereave vent needed
1
.
Instructions
for Slots...
Cut a 2” (5.1cm) slot along
ridge, 1” (2.5cm) on each
side. Leave uncut (closed)
sheathing area of 6”
(15.2cm) at each end
of the ridge.
Cut through the sheathing
only, avoiding roof trusses.
(In houses with a ridge
board, cut 3 1/2” (8.9cm)
slot, 1 3/4” (4.4cm)
on each side.)
(Figure A)
2
.
Ridge Vent
Installation...
Uncoil COBRA
®
EXHAUST VENT along
the entire length of the
ridge, covering uncut 6”
(15.2cm) sheathing area
on both ends.
(Figure B)
Shorter lengths can be
joined by caulking and
butting the ends.
(See Inset Figure B)
3
.
Cap Shingle
Installation...
Install cap shingles directly over COBRA
®
EXHAUST
VENT. Use Smart Nails
(supplied) on centers
recommended by shingle manufacturer. With nail-gun
version, use enclosed gun adapter and 1 3/4" (4.4cm)
included coil nails.
(Figure C)
Do Not overdrive the Smart Nails
.
Cobra
®
Exhaust Vent has a 3/4" (2cm) normal thickness
for optimum ventilation. Be sure not to crush or
compact the product during installation.
(Figure D)
Roof Deck:
Use only over a well-seamed, supported wood deck, tightly constructed with maximum 6” lumber, having
adequate nail-holding capacity. Plywood decking as recommended by the American Plywood Ass’n is acceptable.
Slope Restrictions:
Use only on slopes between 2/12 and 20/12
A
B C
D
© 2003 GAF Materials Corporation 06/03
For a copy of the warranty, contact your local
distributor or visit our website at www.gaf.com
40 YEAR LIMITED WARRANTY
RIDGE VENTS CLASS A CLASSIFIED BY
UNDERWRITERS LABORATORIES INC.
®
AS TO AN
EXTERNAL FIRE EXPOSURE WHEN INSTALLED IN
ACCORDANCE WITH INSTRUCTIONS PROVIDED
WITH RIDGE VENTS 9M61
File R15072
Made from over
90% recycled fiber;
over 30% post-consumer content.
IMPORTANT: Proper
attic ventilation reduces
moisture build-up
and can prevent
mold growth.
Roof Decks:
For use on minimum
3
/
8
"
(10 mm) plywood or oriented strand board (OSB) decking as recommended by APA -The Engineered
Wood Association. Wood plank decks are also acceptable, but must be well-seasoned and supported having a maximum
1
/
8
" (3 mm)
spacing, using minimum nominal 1" (25.4 mm) thick lumber, a maximum 6" (152 mm) width, having adequate nail-holding capacity
and a smooth surface.
Slope Restrictions: Use only on slopes between 2:12 and 20:12.
Step 1 Step 2
Step 3
Instructions
for Slots
Cap Shingle
Installation
Ridge Vent
Installation
Cut a 2" (51 mm) slot along the ridge,
1" (25.4 mm) on each side. Leave
uncut (closed) sheathing area of 6"
(152 mm) at each end of the ridge.
Cut through the sheathing only,
avoiding roof trusses. (In houses
with a ridge board, cut 3
1
/
2
"
[89 mm] slot, 1
3
/
4
"
[44.4 mm]
on each side.) (Figure A)
Uncoil Cobra
®
Exhaust Vent
along the entire length of the
ridge, covering uncut 6"
(152 mm) sheathing area on
both ends. (Figure B)
Shorter lengths can be joined
by caulking and butting the
ends. (See Inset Figure B)
Install cap shingles directly over Cobra
®
Exhaust Vent.
Use enclosed 1
3
/
4
" (44.4 mm) coil nails. (Figure C)
Cobra
®
Exhaust Vent Nail Gun Version has a
5
/
8
"
(15.9 mm) nominal thickness for optimum ventilation.
Be sure not to crush or compact the product during
installation. (Figure D)
NOTE: Nails must be of sufficient length to penetrate
through plywood and OSB decks or at least
3
/
4
"
(19.1 mm) into wood planks.
Please Note The Following:
1. When marking off and cutting slot openings, make sure that
the ends of the opening stop at least 6" (152 mm) from any end
walls and at least 12" (305 mm) from hip and ridge intersections
or chimneys.
2. Where short ridges (dormers, ridge intersections) are used, mark
and cut the slot and make sure that the end of the opening stops
at least 12" (305 mm) from the ridge intersection.
3. Do NOT install on hip roofs.
4. For additional protection in high wind areas, a bead of silicone,
roofing cement, or polyurethane roofing sealant can be applied
around the perimeter of the underside of the cap
shingle before fastening on top of Cobra
®
Exhaust Vent.
Do not use excess roofing cement or polyurethane roofing
sealant, as it may cause blistering of the shingles.
5. For additional protection on installations with extra-thick
shingles, a bead of roofing cement or polyurethane roofing
sealant can be applied to the underside of the outer edge of
the vent along the entire ridge and at exposed edges so that
any large gaps are completely filled. Do not use excess
roofing cement or polyurethane roofing sealant, as it may
cause blistering of the shingles.
Calculations for a Balanced Ventilation System
To achieve a "balanced system" with Cobra
®
Exhaust Vent, there must be an air intake system (i.e., soffits, fascia, or undereave
intake vents). For proper ventilation, the amount of intake ventilation must equal the amount of exhaust ventilation at the ridge.
NOTE: In no case should the amount of exhaust ventilation exceed the amount of intake ventilation.
NOTE: Consult local building codes for other ventilation requirements.
To determine the minimum square feet of net free ventilating area (NFVA) needed for a balanced ventilation system,
use the following formula:
Cobra
®
Exhaust Vent for Nail Gun Installation has 14.1 square inches of NFVA per lineal foot (29,845 mm
2
of NFVA
per lineal meter). To determine how many feet (meters) of Cobra
®
Exhaust Vent is needed, use the following formula:
1
/
2
x (min. sq. ft. of NFVA needed) x 144/14.1 = Min. lineal feet of ridge vent needed
To determine the amount of intake vent required, use the following formula:
X = NFVA (sq. in. per lin. ft.) of the intake vent selected
1
/
2
x (min. sq. ft. of NFVA needed) x 144 /X = Min. lineal feet of intake vents needed
1
/
2
x (min. m
2
of NFVA needed) x 1,000,000/X = Min. lineal meters of intake vents needed
For Roof Ridge
©2019 GAF 7/19 • #092
BA
C
For a copy of the warranty, contact your local
distributor or visit our website at www.gaf.com
40 YEAR LIMITED WARRANTY
RIDGE VENTS CLASS A CLASSIFIED BY
UNDERWRITERS LABORATORIES INC.
®
AS TO AN
EXTERNAL FIRE EXPOSURE WHEN INSTALLED IN
ACCORDANCE WITH INSTRUCTIONS PROVIDED
WITH RIDGE VENTS 9M61
File R15072
Made from over
90% recycled fiber;
over 30% post-consumer content.
IMPORTANT: Proper
attic ventilation reduces
moisture build-up
and can prevent
mold growth.
C
(15.9 mm)
D
5
8
1
/
2
x (min. m
2
of NFVA needed) x 1,000,000/29,845 = Min. lineal meters of ridge vent needed
X = NFVA (mm
2
per lin. m) of the intake vent selected
Sq. ft. of attic floor space = Min. sq. ft. of NFVA needed
300
NOTE: Unless used in conjunction with Cobra
®
Hip Vent, for ridge vent to function properly, it should be the only exhaust vent for
the vented attic space. However, if the ridge vent is being used in conjunction with a hip vent, the total exhaust NFVA should match
the total intake NFVA for the vented attic space. Do not use with gable-end or roof louvers, wind turbines, solar or powered vents,
or other exhaust vents.

Summary of content (3 pages)