Instructions / Assembly

Roof Decks: For use on minimum
3
/
8
"
(10 mm) plywood or oriented strand board (OSB)
decking as recommended by APA - The Engineered Wood Association. Wood plank decks
are also acceptable, but must be well-seasoned and supported having a maximum
1
/
8
"
(3 mm) spacing, using minimum nominal 1" (25 mm) thick lumber, a maximum 6"
(152 mm) width, having adequate nail-holding capacity and a smooth surface.
Slope Restrictions:
Use only on slopes between 3:12 and 16:12.
STEP 1
Calculations for a Balanced Ventilation System
Sq. ft. of attic floor space = Min. sq. ft. of NFVA needed
300
For ridge vent to function properly, it must be the only exhaust vent for the vented attic
space. Do not use with gable-end louvers,turbines, roof vents, or power vents.
To achieve a “balanced system” with Cobra
®
4' (1.21 m) plastic ridge vents, there must be
an air intake system (i.e., soffits, fascia, or undereave intake vents). For proper ventilation,
the amount of intake ventilation must equal the amount of exhaust ventilation at the ridge.
NOTE: Consult local building codes for other ventilation requirements.
NOTE: In no case should the amount of exhaust ventilation exceed the amount of intake ventilation.
To determine the minimum square feet of net free ventilating area (NFVA) needed for
a balanced ventilation system, use the following formula:
Cobra
®
4' (1.21 m) plastic ridge vents have 18.0 square inches of NFVA per lineal foot
(38,100 mm
2
of NFVA per lineal meter). To determine how many feet (meters) of Cobra
®
4' (1.21 m) plastic ridge vent is needed, use the following formula:
1
/
2 x (min. sq. ft. of NFVA needed) x 144/18 = Min. lineal feet of plastic ridge
vent needed
To determine the amount of intake vent required, use the following formula:
X = NFVA (sq. in. per lin. ft.) of the intake vent selected
1
/
2 x (min. sq. ft. of NFVA needed) x 144/X = Min. lineal feet of
intake vents needed
STEP 2
Instruction For Slots
After calculating the total length of Cobra
®
4' (1.21 m) plastic ridge vent needed, determine the
necessary slot opening required.
NOTE: If installing on an existing roof, remove the cap shingles from the ridge.
Roofs without a ridge board: cut a
7
/
8
" (22.2 mm) opening along the ridge on each side (Figure A).
Roofs with a ridge board: cut a 1
5
/
8
"
(41.3 mm) opening along the ridge on each side (Figure B).
Note: Maximum slot opening is 3
1
/
4
" (83 mm) wide.
Mark off and cut the slot opening, making sure that the ends of the opening stop at least 6"
(152 mm) from any end walls and 12" (305 mm) from hip and ridge intersections or chimneys
(Figure C).
Where short ridges (dormers, ridge intersections) are used, mark and cut the slot making sure
that the end of the opening stops at least 12" (305 mm) from the ridge intersection (Figure D).
RIDGERUNNER
Roof Deck: Use only over a well-seasoned, supported wood deck, tightly constructed with
maximum 6" wide lumber, having adequate nail-holding capacity. Plywood decking as
recommended by The Engineered Wood Association is acceptable.
For ridge vent to function properly, it must be the only high or exhaust vent for the vented
attic space. Do not use with gable-end louvers, turbines, roof vents or power vents.
Slope Restrictions: Use only on slopes between 3/12 and 16/12.
STEP 1
Calculations for a Balanced Ventilation System
To achieve a “balanced system with Cobra
®
Ridge Runner
ridge vent, there must be
an air intake system (i.e., soffit or undereave vents). For proper ventilation, the amount
of undereave ventilation must equal the amount of ventilation at the ridge.
NOTE: Consult local building codes for other ventilation requirements.
NOTE: In no case should the amount of exhaust ventilation exceed the amount of intake ventilation.
To determine the minimum square feet of net free ventilating area (NFVA)
needed for a balanced ventilation system, use the following formula:
Cobra
®
Ridge Runner
ridge vent has 12.5 square inches of NFVA per lineal
foot. To determine how many feet of Cobra
®
Ridge Runner
ridge vent is
needed, use the following formula:
1/2 x (Min. Sq. ft. of NFVA needed) x 144/12.5 = Min. lineal feet of ridge vent needed.
To determine the amount of undereave vent required, use the following formula:
X = NFVA (Sq. in. per. lin. ft.) of the undereave vent or intake vent system selected
1/2 x (Min. Sq. Ft. of NFVA needed) x 144/X = Min. lineal feet of undereave
vent needed.
APPLICATION INSTRUCTIONS
Exhaust Vent For Ridge Roof
STEP 2
Instruction For Slots
After calculating the total length of Cobra
®
Ridge Runner
ridge vent needed, determine
the necessary slot opening required.
Note: If installing on an existing roof, remove the cap shingles from the ridge.
Roofs without a ridge board: cut an opening along the ridge
7
/
8
" on each side (Figure A).
Roofs with a ridge board: cut an opening along the ridge 1
5
/
8
" on each side (Figure B).
Note: Maximum slot opening is 3
1
/
4
" wide.
Mark off and cut the slot opening, making sure that the ends of the opening stop at least
6" from any end walls and 12" from chimneys and hip intersections (Figure C).
Where short ridges (dormers, ridge intersections) are used, mark and cut the slot making
sure that the end of the opening stops at least 12" from the ridge intersection (Figure D).
5
/
8
1
5
/
8
1
Fig. A
Fig. B
Fig. C
Fig. D
Sq. ft. of attic floor space
Min. Sq. ft. of NFVA needed
300
=
20'x11
1
/2" Roll
1
/
4
3
(22.2 mm) (22.2 mm)
(44.4 mm)
(41.3 mm) (41.3 mm)
(83 mm)
(152 mm) (305 mm) (152 mm) (305 mm)
(152 mm) (152 mm)
(305 mm)
(152 mm) (152 mm)
(152 mm)
" "
"
"
"
"
Installation Instructions
Exhaust Vent For Roof Ridge
Exhaust Vent For Roof Ridge
SNOWCOUNTRY
®
®
SNOWCOUNTRY
A D V A N C E D
®
SNOWCOUNTRY
A D V A N C E D
®
SNOWCOUNTRY
A D V A N C E D
®
®
SNOWCOUNTRY
A D V A N C E D
SNOWCOUNTRY
A
D V A N C E D
NOTE:
Unless used with Cobra
®
Hip Vent, for ridge vent to function properly, it should be the only
exhaust vent for the vented attic space. However, if the ridge vent is being used in conjunction with
a hip vent, the total exhaust NFVA should match the total intake NFVA for the vented attic space. Do
not use with gable-end or roof louvers, wind turbines, solar or powered vents, or other exhaust vents.
NOTE:
GAF recommends the use of properly installed filtered ridge vents in geographic areas prone to
regular snowfall, as well as those “borderline” areas that may experience snowfall, albeit infrequently.
1
/
2 x (min. m
2
of NFVA needed) x 1,000,000/38,100 = Min. lineal meters
of plastic ridge vent needed
X = NFVA (mm
2
per lin. m) of the intake vent selected
1
/
2
x (min. m
2
of NFVA needed) x 1,000,000/X = Min. lineal
meters of intake vents needed

Summary of content (6 pages)