Instructions / Assembly
Quick Specs
HydroStop® PremiumCoat® Liquid-Applied Roong (LAR) – Version 1.3
21
Substrate Preparaon: PVC & Hypalon®
Areas of Concern Treatment
Parapet Walls
•
Repair all open seams and any loose or failed terminaons with in-
kind materials prior to applicaon of HydroStop® PremiumCoat®
Buer Grade Flashing with fabric.
•
All parapet wall details within the roof system must be secured
and sealed with a 12 inch (305 mm) minimum width of
HydroStop® PremiumCoat® Buer Grade Flashing with fabric.
•
Fabric must be cut around all fasteners so it lies at.
Curb Flashings
•
All curb ashings, including cricket details, must be ashed with
at least a 12 inch (305 mm) width of HydroStop® PremiumCoat®
Buer Grade Flashing with fabric.
•
Encapsulate all fasteners using HydroStop® PremiumCoat® Buer
Grade Flashing with fabric. Do not bridge fasteners.
•
Fabric must be cut around all fasteners so it lies at.
Penetraons
•
HydroStop® PremiumCoat® Buer Grade Flashing with fabric must
be applied around the base of all penetraons, extending at least
6 inches (152 mm) up the vercal and 6 inches (152 mm) onto the
base.
•
Cut the fabric to accommodate the shape of the penetraon.
Skylights
•
Curb skylights must be treated in the same fashion as curb
ashings.
•
Aer ashing work has been completed and the coang has cured,
treat deteriorated berglass skylight panels with United Coangs™
Acrysheen Sealer.
Pitch Pans
•
Pitch pans must be capped with sheet metal so that they may be
sealed with HydroStop® PremiumCoat® Buer Grade Flashing.
Condensate Lines
•
Condensate lines must be installed from HVAC units to guers as
part of the overall drainage system. The type of piping used for
condensate lines may vary depending on local building codes.