Instructions / Assembly
Quick Specs
HydroStop® PremiumCoat® Liquid-Applied Roong (LAR) – Version 1.3
35
QUICK SPEC
STRUCTURAL CONCRETE – HYDROSTOP® PREMIUMCOAT® (HS-7)
Method
Requirements
Applicaon
Instrucons
• Moisture survey required.
• Roof must be clean, dry, and tight.
• Adhesion test required to ensure proper adhesion to substrate(s).
• Apply at 50°F (10°C) and rising with no rain, dew, fog or freezing temperatures
in forecast for 24 hours.
• GAF recommends that the surface temperature be at or less than 110°F (43°C)
during application.
• Concrete must be fully cured (typically 28 days).
1. Before applying the HydroStop® PremiumCoat® System, an adhesion test is
required to ensure an adhesion of a minimum of 2.0 PLI. Test patches to be
applied with system rates listed below.
2. Conduct moisture survey to ensure concrete contains less than 8% moisture.
3. Repair or replace damaged or deteriorated secons with like materials, allowing
cemenous products to cure properly.
4. Power wash roof to ensure it is free of dirt, debris, oil, and other contaminants
that could negavely aect adhesion. United Cleaning Concentrate (UCC) is
recommended to clean the roof. Allow roof to completely dry.
5. Prime with Epoxy Primer.
6. Treat structural joints with backer rod and compable sealant.
7. Control joints in excess of 1/16” (1.6mm) shall also be caulked with a compable caulk.
8. Treat all roof penetraons, drains, curbs, caulked control joints, and scuppers.
9. Apply HydroStop® PremiumCoat® Foundaon Coat and Finish Coat per the chart
below.
• Use GAF Roof Brush to apply HydroStop® PremiumCoat® Foundaon Coat
• Spray, roller, or brush apply HydroStop® PremiumCoat® Finish Coat
NOTE: The following “Quick Spec” is an abbreviated specicaon and is not meant to replace the detailed
specicaon. Read the enre 3-Part CSI System Specicaon prior to starng the project. Specicaons are
available at www.gaf.com.
SEAMS & DETAILS | HYDROSTOP® PREMIUMCOAT® SYSTEM
Treatment Type Product
Total
(Gal/Sq)
DFT*
(mils)
3-Coursed Rates HydroStop® Buer Grade and Fabric 4.0 43
Flashing Grade Only Rates HydroStop® Buer Grade 2.0 19
STRUCTURAL CONCRETE
HYDROSTOP® PREMIUMCOAT® SYSTEM
Foundaon Coat
(with fabric)
Finish Coat System Warranty
Total
(Gal/Sq)
DFT*
(mils)
1st Coat
(Gal/Sq)
2nd Coat
(Gal/Sq)
3rd Coat
(Gal/Sq)
Total
(Gal/Sq)
DFT*
(mils)
Total
(Gal/Sq)
DFT*
(mils)
Emerald
Pledge™
Diamond
Pledge™
10 Year 2.5 27 0.75 0.75 1.50 13 4.00 40 Yes Yes
15 Year 2.5 27 1.00 1.00 2.00 17 4.50 44 Yes Yes
20 Year 2.5 27 1.00 1.00 1.00 3.00 25 5.50 52 Yes Yes
* Dry Film Thickness (DFT) is rounded to nearest mil, and is theorecal. Actual DFT will vary dependent on substrate prole, applicaon
technique and waste factor.
Note: DFT for 3-coursed rates includes 6 mils for the fabric.