User's Manual

16 Part number 3E1100 R12
June 2007
Initialise Process
!
CAUTION
Do not fit the lithium battery jumper (J1) before powering
up the URI. If the jumper is fitted you must remove it and
wait 10 seconds.
Power up the URI.
The yellow LED (D45) should be permanently ON. This indicates that 5 V is
present on the board.
The green LED (D44) should flash twice, pause, then flash twice again. This is
a continuous sequence while the URI is unitialised and indicates it is
processing.
The red LED (D8) should flash if polls are received from the Commander.
Note:
A URI can be initialised without being connected to a Commander.
Set DIPSW1:7 to ON.
Present a Smart Card to the Prox Mifare Series (Teardrop) reader.
Note:
You must present the card within 30 seconds of setting DIPSW1:7 to ON. If
you are initialising with two readers connected to the URI, you should present
the card to the reader on URI plug P5.
Set DIPSW1:7 to OFF
The green LED (D44) will begin flashing continuously.
The other red LED (D10) will flash each time the URI replies to a poll from the
Commander.
Replace the lithium battery jumper J1.
Restore the tamper by closing the door of the URI cabinet.