3E4288 Gallagher T10 Reader | Edion 1 | August 2016
Copyright © Gallagher Group Limited
HBUS
Device
"T" or "Star" circuits are
not permied between
HBUS devices
Controller 6000
H1
H4
H8
H5
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS Module
HBUS
Device
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS
Device
Cabledistance
Cabletype Cableformat* HBUS
single reader
connected using
dataonlyina
singlecable
Cardax IV
single reader
connected using
dataonlyina
singlecable
HBUS/Cardax IV
single reader
connected using
power and data
inasinglecable
CAT 5e or
beer**
4 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
BELDEN 9842**
(shielded)
2 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
SEC472 4 x 0.2 mm
2
Not twisted
pairs (24 AWG)
400 m (1310 ) 200 m (650 ) 100 m (330 )
SEC4142 4 x 0.4 mm
2
Not twisted
pairs (21 AWG)
400 m (1310 ) 200 m (650 ) 150 m (500 )
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for opmal HBUS RS485 performance.
Notes:
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
If other cable types are used, operang distances and performance may be reduced
depending on the cable quality.
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to funcon correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.