Installation Instructions

Page 7
3E4289 Gallagher T11 Reader | Edion 1 | August 2016
Copyright © Gallagher Group Limited
Cabledistance
Cabletype Cableformat* HBUS
single reader
connected using
dataonlyina
singlecable
Cardax IV
single reader
connected using
dataonlyina
singlecable***
HBUS/Cardax IV
single reader
connected using
power and data
inasinglecable
CAT 5e or
beer**
4 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
BELDEN 9842**
(shielded)
2 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
SEC472 4 x 0.2 mm
2
Not twisted
pairs (24 AWG)
400 m (1310 ) 200 m (650 ) 100 m (330 )
SEC4142 4 x 0.4 mm
2
Not twisted
pairs (21 AWG)
400 m (1310 ) 200 m (650 ) 150 m (500 )
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for opmal HBUS RS485 performance.
*** Not applicable for PIV or Gallagher mobile credenal reader installaons.
Notes:
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
If other cable types are used, operang distances and performance may be reduced
depending on the cable quality.
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to funcon correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3 Distancebetweenreaders
The distance separang any two proximity readers must not be less than 200 mm (8 in) in all direcons.
When mounng a proximity reader on an internal wall, check that any reader xed to the other side of
the wall is not less than 200 mm (8 in) away.
200 mm
200 mm