Installation Instructions
Table Of Contents
Page 7
3E4289 Gallagher T11 Reader | Edion 1 | August 2016
Copyright © Gallagher Group Limited
Cabledistance
Cabletype Cableformat* HBUS
single reader
connected using
dataonlyina
singlecable
Cardax IV
single reader
connected using
dataonlyina
singlecable***
HBUS/Cardax IV
single reader
connected using
power and data
inasinglecable
CAT 5e or
beer**
4 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
BELDEN 9842**
(shielded)
2 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
SEC472 4 x 0.2 mm
2
Not twisted
pairs (24 AWG)
400 m (1310 ) 200 m (650 ) 100 m (330 )
SEC4142 4 x 0.4 mm
2
Not twisted
pairs (21 AWG)
400 m (1310 ) 200 m (650 ) 150 m (500 )
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for opmal HBUS RS485 performance.
*** Not applicable for PIV or Gallagher mobile credenal reader installaons.
Notes:
• Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
• If other cable types are used, operang distances and performance may be reduced
depending on the cable quality.
• HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to funcon correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3 Distancebetweenreaders
The distance separang any two proximity readers must not be less than 200 mm (8 in) in all direcons.
When mounng a proximity reader on an internal wall, check that any reader xed to the other side of
the wall is not less than 200 mm (8 in) away.
200 mm
200 mm