2.2 Powersupply
The Gallagher T12 Reader is designed to operate over a supply voltage range of 9 - 16 Vdc
measured at the reader terminals. The operang current draw is dependant on the supply
voltage at the reader. For the Mifare reader, at 13.6 Vdc the current draw is 84 mA (idle). During
card read, beeper and LED acvity, the current will momentarily reach 113 mA (maximum). For
the Mul Tech reader, at 13.6 Vdc the current draw is 100 mA (idle) and will momentarily reach
124 mA (maximum). The power source should be linear or a good quality switched-mode power
supply. The performance of the reader may be aected by a low quality, noisy power supply.
2.3 Cabling
The Gallagher T12 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm
2
) stranded
security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When
using a single cable to carry both power supply and data, both the power supply voltage drop
and data requirements must be considered. Although the reader is specied to operate at 9
Vdc, for good engineering design it is recommended that the voltage at the reader should be
approximately 12 Vdc.
HBUScablingtopology
The HBUS communicaons protocol is based on the RS485 standard and allows the reader to
communicate over a distance of up to 500 m (1640 ).
The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or
"Star" topology should not be used between devices). Should "Star" or "Home-Run" wiring be
required, the HBUS 4H/8H Modules and the HBUS Door Module allow mulple HBUS devices to
be individually wired to the one physical locaon.
The end devices on the HBUS cable should be terminated using 120 ohms resistance. To
terminate the Gallagher Controller 6000, connect the supplied on-board terminaon jumpers
to the Controller. To terminate a reader, connect the orange (terminaon) wire to the green
(HBUS A) wire. Terminaon is already included at the HBUS Module, (i.e. each HBUS port is
permanently terminated at the module).
Connect the on-board
terminaon jumper
Controller 6000
RS485 1
HBUS
Device
"T" or "Star" circuits are
not permied between
HBUS devices
HBUS
Device
Terminate
HBUS
Device
HBUS
Device
HBUS
Device