User's Manual
Table Of Contents
- 1. General
- 2. Mounting the GAT Access 6100 Terminals
- 3. Electrical Connections
- 4. Start-up and Configuration
- 5. Operation
- 5.1 Control and Display Elements
- 5.2 General
- 5.3 User Operation at a GAT Access 6100
- 5.4 User Operation at a GAT Access 6100 F BIO
- 5.5 User Operation at a GAT Access 6100 F Enrollment Station
- 5.6 Standard Operation for the GAT TimeAxx 6150 with Countdown Functionality
- 5.7 Online Mode and Emergency Mode
- 5.8 Out of Order Screen
- 5.9 Locker Check-In
- 5.10 General Open Function (Group Entry)
- 5.11 External Release Function
- 6. Communication
- 7. Updating the GAT ACCESS 6100
- 8. Troubleshooting and FAQ
- 8.1 How can I update the firmware of a GAT Access 6100?
- 8.2 How do I configure a GAT Access 6100?
- 8.3 Which TCP/IP ports can be used by a GAT Access 6100?
- 8.4 Which bit rates are used by a GAT Access 6100 for Ethernet and is this configurable?
- 8.5 How can I set the date and time of a GAT Access 6100?
- 8.6 How can I find the IP address of a GAT Access 6100 and change it?
- 8.7 How can I find the MAC address of a GAT Access 6100?
- 8.8 Setting IP address when MAC address is not known and IP address of the terminal is 0.0.0.0
- 8.9 Difference between "Time" and "Delay" in the "Mode" field for Locker Check-In configuration?
- 8.10 Meaning of optocoupler settings "Rising_Edge", "Falling_Edge", "Rising- and Falling Edge"?
- 8.11 How can the reader of a GAT Access 6100 B be authorised for LEGICĀ®?
- 8.12 How can I read or delete the authorisation data of a GAT Access 6100?
- 8.13 How can I configure the display texts of a GAT Access 6100?
- 8.14 The relay of the GAT Access 6100 is activated even if the host has denied access.
- 8.15 Which FUNLINE protocol commands are supported by a GAT Access 6100?
- 8.16 Why does the GAT Access 6100 deny access with my data carrier in Emergency mode?
- 8.17 What is the maximum start-up current consumption of a GAT Access 6100?
- 8.18 What are the factory settings of a GAT Access 6100?
- 8.19 How do I configure a GAT Access 6100 for offline emergency mode?
- 8.20 What is the data carrier certificate?
- 9. Technical Data

GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150
Mounting the GAT Access 6100 Terminals
24
HB_GAT-ACCESS6100--EN_12
www.gantner.com
1. Insert the FX tube (12) with the connection cable (3) into the opening of the back box. The opening is designed
for an FX tube with 25 mm outer diameter. In this case, the lugs (13) at the opening are holding the FX tube in
place.
2. Insert the back box (10) into the wall recess (11) and make sure, that it is flush with the wall surface (see 15).
Fix the back box e.g. with plaster or PU foam (14).
3. Feed the connection cable (3) through the opening of the GAT TimeAxx 6150 back part.
4. Caulk the edge of the cable opening in the GAT TimeAxx 6150 back part with silicone (1) -> see also step 1 at
the description of the surface mounting.
5. Mount the GAT TimeAxx 6150 into the back box by using three screws (2). This is done the same way as
described in Step 2 of the surface mounting. Pay attention, that the cable opening is completely sealed with the
previously applied silicone.
6. The remaining mounting procedure is the same as described at the surface mounting, beginning with step 3
onward.
Attention: To finish the installation the GAT TimeAxx 6150 must be hermetically sealed. Humidity/water
must never be able to penetrate into the housing. Pay special attention that the silicone
applied in step 4 seals the housing completely and that the rubber seal (see step 4 of surface
mounting) is inserted correctly and seals the housing in its entire length.
b) Installation in Concrete Walls
1. Unscrew the four screws of the back box (16) and remove them, together with the metal lugs.