Install Instructions

GASTITE DIVISION, TITEFLEX CORPORATION / 1116 Vaughn Parkway / Portland, TN 37148
800.662.0208 / www.gastite.com / gastite@gastite.com
24
SECTION 3: SYSTEM CONFIGURATION / JANUARY 2019
SIZING RUN “C”
Run “C” is sized by the load of the supplied appliance and the run length to the supplied appliance
e load of the water heater is 36CFH
e run length to the water heater is 45 + 10 = 55ft
Referring to Table 7-2 (1.0"WC pressure drop) for a 60ft run, 1/2" CSST has a capacity over 36CFH (actual: 54)
SIZING RUN “D”
Run “D” is sized by the load of the supplied appliance and the run length to the supplied appliance
e load of the range is 52CFH
e run length to the range is 45 + 20 = 65ft
Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 3/4" CSST has a capacity over 52CFH (actual: 103)
SIZING RUN “E”
Run “E” is sized by the total load of all supplied appliances and the run length from the meter to the furthest appliance
e total load of the BBQ and the dryer is 25 + 28 = 53CFH
e run length to the BBQ (furthest appliance) is 45 + 20 + 5 = 70ft
Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 3/4" CSST has a capacity over 53CFH (actual: 103)
SIZING RUN “F”
Run “F” is sized by the load of the supplied appliance and the run length to the supplied appliance
e load of the dryer is 28CFH
e run length to the dryer is 45 + 20 + 5 = 70ft
Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 1/2" CSST has a capacity over 28CFH (actual: 50)
SIZING RUN “G”
Run “G” is sized by the total load of the supplied appliance and the run length from the meter to the furthest appliance
e load of the BBQ is 25CFH
e run length to the BBQ is 45 + 20 + 5 = 70ft
Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 1/2" CSST has a capacity over 25CFH (actual: 50)