Install Instructions

GASTITE DIVISION, TITEFLEX CORPORATION / 1116 Vaughn Parkway / Portland, TN 37148
800.662.0208 / www.gastite.com / gastite@gastite.com
75
SECTION 7: SIZING TABLES & PRESSURE DROP CHARTS / JANUARY 2019
Table 7-3
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 1.5"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 83 58 47 40 36 32 28 25 22 21 19 18 17 15 14
19 1/2" 226 160 131 114 102 93 81 72 66 61 57 54 51 46 42
23 3/4" 416 303 251 220 199 183 160 145 133 124 116 110 105 95 87
31 1" 981 703 578 504 452 415 361 324 297 276 259 244 232 209 191
37 1-1/4" 1493 1063 871 757 678 620 539 483 441 409 383 362 344 308 282
48 1-1/2" 3152 2240 1834 1592 1426 1304 1131 1014 926 859 804 759 720 645 590
60 2" 6825 4775 3874 3340 2978 2711 2337 2083 1896 1752 1635 1539 1457 1299 1183
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 12 11 10 8 7 7 6 6 5 5 5 5 4 4 4
19 1/2" 37 33 30 26 23 21 20 18 17 17 16 15 15 14 14
23 3/4" 76 69 63 56 50 46 43 40 38 37 35 34 32 31 30
31 1" 167 150 137 119 107 98 91 86 81 77 73 70 68 65 63
37 1-1/4" 245 219 201 174 156 143 132 124 117 111 106 102 98 94 91
48 1-1/2" 512 459 419 364 326 298 276 259 244 232 221 212 204 196 190
60 2" 1020 909 827 713 636 579 535 499 470 445 424 405 389 374 361
Table 7-4
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 2.0"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 97 67 54 47 41 38 32 29 26 24 22 21 20 18 16
19 1/2" 260 185 151 131 118 107 93 83 76 71 66 62 59 53 49
23 3/4" 475 345 287 251 227 209 183 165 152 141 133 126 120 108 100
31 1" 1126 807 664 578 520 476 415 372 341 317 297 281 267 240 220
37 1-1/4" 1719 1224 1003 871 781 714 620 556 508 471 441 417 396 355 324
48 1-1/2" 3632 2581 2114 1834 1643 1502 1304 1168 1068 989 926 874 830 744 680
60 2" 7915 5538 4493 3874 3453 3144 2711 2416 2199 2031 1896 1785 1690 1507 1372
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 14 12 11 10 8 8 7 7 6 6 6 5 5 5 5
19 1/2" 42 38 34 30 27 24 23 21 20 19 18 17 17 16 16
23 3/4" 87 79 72 63 57 53 49 46 44 42 40 38 37 36 35
31 1" 191 172 157 137 123 113 105 98 93 88 84 81 78 75 73
37 1-1/4" 282 253 231 201 180 164 152 143 135 128 122 117 113 109 105
48 1-1/2" 590 528 483 419 376 343 318 298 281 267 255 244 235 226 219
60 2" 1183 1054 960 827 737 671 620 579 545 516 491 470 451 434 419
Tables include losses for four 90° bends and two end fittings. Tubing runs with a larger number of bends and/or fittings shall be increased by an equivalent
length of tubing to the following equation: L=1.3n where L is additional length of tubing and n is the number of additional fittings and/or bends.