Logic HE Range Conventional Flue Log Effect Installation User Instructions

18
Installation Instructions
2.4 This appliance must stand on a non-combustible hearth that
is at least 12mm thick.
2.5 If the appliance is greater than 50mm above the floor, then
no hearth is required, although due consideration should be
given to how the heat may affect the floor material.
2.6 Ensure that no naked flame or incandescent part of the fire bed
projects beyond the vertical plane of the fireplace opening.
2.7 The appliance must not be installed in any room that
contains a bath or shower.
2.8 Ensure clearances to combustible materials, see Diagram 2.
Dimensions
given are to the
decorative front
of the appliance.
2
150
150
150
2.9 The maximum depth of combustible shelf is 150mm at a
minimum height of 150mm above the decorative front.
Refer to the appropriate Frame Instructions regarding
additional wall strengthening for the frame.
3. Gas Supply
3.1 Make sure local distribution conditions (identification of
the type of gas and pressure) and the adjustment of the
appliance are compatible before installation.
3.2 Ensure the gas supply delivers the required amount of gas
and is in accordance with the rules in force.
3.3 This appliance is supplied complete with a factory fitted
isolation device incorporated into the inlet connection, no
further isolation device is therefore required.
4. Ventilation
IMPORTANT: Ensure any national ventilation
requirements are taken into account during installation
of the appliance.
4.1 This appliance has a nominal input not exceeding 7.0kW
and therefore does not normally require any additional
permanent ventilation. If, however, spillage is detected when
commissioning the appliance, there may be insufficient
natural ventilation and additional ventilation may be
required.
FOR THE REPUBLIC OF IRELAND REFER TO THE
RULES IN FORCE FOR VENTILATION REQUIREMENTS.
AIR VENTS MUST NOT BE RESTRICTED.
Site Requirements