Reflex 105 Multi-Sided Inset Convector Fire Range with Harmony 10 Remote Control System Installation Instructions IMPORTANT THE OUTER CASING, FRONT AND GLASS PANEL BECOME EXTREMELY HOT DURING OPERATION AND WILL RESULT IN SERIOUS INJURY AND BURNS IF TOUCHED. IT IS THEREFORE RECOMMENDED THAT A FIREGUARD COMPLYING WITH BS 8423 (LATEST EDITION) IS USED IN THE PRESENCE OF YOUNG CHILDREN, THE ELDERLY OR INFIRM. This product contains a Heat resistant glass panel.
CONTENTS REFLEX 105 MULTI-SIDED - BALANCED FLUE NAT GAS LPG 191-014 191-405 Appliance Commissioning Checklist.......................3 User Instructions........................................................4 Installation Instructions...........................................11 Technical Specifications ........................................................... 14 Installation................................................................................. 22 Commissioning..............................
APPLIANCE COMMISSIONING CHECKLIST To assist us in any guarantee claim please complete the following information:- IMPORTANT NOTICE Explain the operation of the appliance to the end user, hand the completed instructions to them for safe keeping, as the information will be required when making any guaranteed claims. FLUE CHECK PASS FAIL 1. Flue Is correct for appliance 2. Flue flow Test N/A 3. Spillage Test N/A GAS CHECK 1. Gas soundness & let by test 2. Standing gas pressure mb 3.
GENERAL Installation and servicing must only be carried out by a competent person whose name appears on the Gas Safe register. To ensure the engineer is registered with Gas Safe they should possess an ID Card carrying the following logo: In all correspondence, please quote the appliance type and serial number, which can be found on the data badge located on a plate under the Main Burner.
OPERATING THE APPLIANCE TURNING THE APPLIANCE ON The appliance is operated by thermostatic and programmable remote control. The handset controls the appliance from pilot ignition through to shut down. To turn the fire on press the button until two short signals and a series of blinking series of lines confirm the start of the ignition sequence. The pilot will ignite and the remote is now in Manual Mode: IMPORTANT: YELLOW FLAMES TYPICALLY APPEAR WHEN THE APPLIANCE HAS REACHED NORMAL OPERATING TEMPERATURE.
TURNING THE APPLIANCE OFF (STANDBY) Press and hold the button to turn the appliance off. NOTE: There is a 5 second delay before the next ignition is possible. MANUAL MODE Exiting Thermostatic Mode: Press the button to exit Thermostatic mode. Press the or Press the button to enter Program Mode. Press the button to enter EcoFlex Mode. button to enter Manual Mode.
Select the minutes by pressing the Press the or button. button to confirm. NOTE: either continue to PROGRAM 2 and set on and off times or stop programming at this point and PROGRAM 2 remains deactivated. PROGRAM 1 and PROGRAM 2 use the same On (Thermostatic) and Off temperatures for ALL, SA:SU and Daily Timer (1, 2, 3, 4, 5, 6, 7). Once a new On (Thermostatic) and/or Off temperature has been set, that temperature becomes the new default setting.
SETTING FAHRENHEIT OR CELSIUS COUNTDOWN TIMER Turning the Timer on. Press and hold the flashes. button until To select the hour press the To confirm press the or button. button. Minutes flash. To select the minutes press the To confirm press the displayed, and hour or button. button or wait. Turning the Timer off. Press and hold the disappear. button, and countdown display will At the end of countdown time period, the appliance turns off.
3. If there are any changes to the home network then the MyFire Wi-Fi set up must be repeated. Quick Reference Table - for LED. LED INDICATOR FOR MYFIRE WI-FI BOX LABEL LED Power Blue WLAN Green Receiver Blue All LEDs CLEANING THE APPLIANCE From time to time it may be necessary to remove build up of debris and soot from the logs. STATUS Make sure the appliance and surrounds are cool before cleaning. On Power On Remove the side trims and lower trim from the appliance.
The Front Glass can now be removed. Carefully move the front glass into the gap, then lift and manoeuvre the bottom outwards to remove. 1 RUNNING IN During initial use of a new Gazco appliance a strong odour will be encountered as various surface coatings become hot for the first time. Although these odours are harmless it is recommended that the appliance is operated on maximum for 4 to 8 hours in order to fully burn off these coatings. After this period the odours should then disappear.
INSTALLATION APPLIANCE LOCATION This appliance must only be fitted into a studwork installation. This appliance must not be installed in a room that contains a bath or shower. Combustible parts of the studwork must not be any closer than the minimum dimensions shown in the diagrams. NOTE: These dimensions must be maintained even if the combustible materials is protected by non-combustible linings. Do not pack the void around or above the appliance with insulation materials such as mineral wool.
FLUE & CHIMNEY REQUIREMENTS Note: This appliance must only be installed with the flue supplied. The following: must be adhered to: The flue must be sited in accordance with BS5440: Part 1 (latest edition). Fit a guard to protect people from any terminal less than 2 metres above any access such as level ground, a balcony or above a flat roof. All vertical and horizontal flues must be securely fixed and fire precautions followed in accordance with local and national codes of practice.
DIMENSIONS 239 976 586 138 1136 1211 1237 203 432 358 232 586 50 358 899 962 51 13
TECHNICAL SPECIFICATION Covering the following models: NAT GAS LPG 191-014 191-405 GAS CAT. GAS TYPE WORKING PRESSURE GAS RATE M3/H Reflex 105 I2H Nat Gas G20 19mbar 1.191 Reflex 105 I3+ Propane G31 36mbar 0.508 Butane G30 28mbar 0.386 MODEL INPUT KW (GROSS) HIGH LOW 12.5 5.9 13.5 5.
TECHNICAL SPECIFICATION INJECTOR TABLE REAR REAR REAR REAR Nat Gas S104 Nat Gas S128 Nat Gas S102 Nat Gas 110 LPG S78 LPG S80 LPG S60 LPG 109 Rear of appliance Front of appliance FRONT FRONT Nat Gas S92 LPG S60 FRONT FRONT Nat Gas S92 LPG Nat Gas S88 S58 LPG S58 Nat Gas 88 LPG 58 AERATION TABLE NOTE: Aeration plates are on each leg of the burners. These holes are different sizes at the Front and Back for each individual leg. REAR REAR REAR Nat Gas 5.
TECHNICAL SPECIFICATION RESTRICTOR TABLES RESTRICTOR REQUIREMENT - VERTICAL & HORIZONTAL FLUE SPECIFICATION REFLEX 105 Vertical flue height from top of appliance Horizontal length 1000mm - 1499mm 1500mm - 3000mmm Restrictor size NG LPG up to 6000mm 90 - up to 6000mm 85 90 TOP EXIT - VERTICAL ONLY INCLUDING OFFSET (8" WITH 6" ADAPTER) Vertical flue height from top of appliance NG LPG 1500mm - 2999mm 80mm 90mm 3000mm - 5999mm 75mm 80mm 6000mm - 10000mm 70mm 70mm This appliance has been
Earth Mains Power In Light Supply LED Ignition Lead Thermocouple Electric Module Pilot Burner Control Box SW Lead Control Value Control Valve Supply Wi-Fi Module (Optional) Solenoid Supply Lead TC Lead Solenoid Valve WIRING DIAGRAM 17
FLUE OPTIONS All flue installations must be constructed in accordance with the rules in force. UK - Building Regulations: Approved Document J. 8" TOP FLUE UP AND OUT KIT (999-333/999-333AN) NOTE: This product is designed for and requires an 8" flue system. It is essential when ordering additional parts to consult table 1 for the relevant part numbers. A masonry installation requires the addition of a suitable lintel to support the opening.
FLUE OPTIONS TOP FLUE VERTICAL KIT (999-352/999-352AN) NOTE: This product is designed for and requires an 6" flue system. It is essential when ordering additional parts to consult table 2 for the relevant part numbers. This flue is vertical from the top of the appliance, see Diagram. A minimum vertical rise of 1.5m to a maximum of 10m.
MOUNTING BRACKET 1 REMOVING THE MOUNTING BRACKET This appliance weighs 110Kg. The manufacturer has designed this appliance to attach to a masonry wall and all fixings supplied reflect this. However if desired it is possible to locate the Reflex on a non-combustible studwork wall providing it is constructed to give adequate load baring support. If intending to install the appliance on a studwork wall it is essential that the battens are located across the fixing areas of the wall mounting bracket.
MOUNTING BRACKET MOUNTING BRACKET CLEARANCES Floor Mounted Combustible Material 836mm min Combustible Material Combustible Material 200mm 200mm 903mm Floor Wall Mounted Side Wall 200mm Minimum 138mm From viewing area 250mm Minimum for Wall Mounted installation Floor Level 21
PRE-INSTALLATION REMOVING THE GLASS 4 1 5 Top Support Bracket Gap 2 Bottom Support Bracket Gap 6 1 3 Top Pivot Brackets 2 Bottom Pivot Brackets 22 The side glass does not need to be removed to install the appliance. It is recommended to leave the Side Glass in situ unless absolutely necessary.
REMOVING THE MAIN CONTROL ASSEMBLY 5 The Main Control Assembly will need to be removed to install the gas supply. 1 6 2 Disconnect the Mains Lead Plug, the LED leads and the receiver lead from the Module and the Wi-Fi box (if installed). DO NOT REMOVE THE WIRES FROM THE PLUG.
The appliance stands off the wall by 55mm. It will be necessary to build a studwork enclosure to house the mounting bracket and separate enclosures for the upper and lower faces of the appliance. 9 WARNING: This appliance weighs 108Kg. The manufacturer has designed this appliance to attach to a masonry wall and all fixings supplied reflect this. If siting on a studwork wall, the fixing points must be through the timber stud and not plasterboard. Use appropriate fixings.
Once satisfied with the position of the appliance, tighten the 2 nuts on either side of the fire. 14 16 If required, use the two adjustment bolts at the rear of the appliance to alter the vertical position of the fire. Fit the flue. 15 Wall Bracket removed for clarity Run the mains power lead out of the right side of the appliance.
FLUE ASSEMBLY TAKE CARE WHEN MARKING OUT FOR THE FLUE AS IT IS DIFFICULT TO MOVE AFTER INSTALLATION. IF A RESTRICTOR IS REQUIRED FIT THIS BETWEEN THE SMALL OUTLET SPIGOT AND THE AIR DUCT. REFER TO TECHNICAL SPECIFICATIONS FOR RESTRICTOR SIZE. A 208mm diameter hole in the wall is required to install the flue. This can be achieved by using either: a) Core drill b) Hammer and chisel Drill small holes around the circumference when using method b). Make good both ends of the hole.
ENCLOSURE CONSTRUCTION 3 SIDED INSTALLATION Example enclosure VENTILATION Note: If the lower section of the enclosure is sealed (to the floor or capped if designed as a floating shelf) it will be necessary to provide a vent with a free area of 150cm2 on each side. If the upper section is sealed (to the ceiling or capped if designed as a floating shelf) it will be necessary to provide a vent with a free area of 400cm2 on each side.
3 SIDED INSTALLATION CUTTING TEMPLATES B B Upper Front Panel Side Panel x2 E A C B Lower Front Panel D A A D Inner Side Panel B C B Base Panel A A D B C Upper Inner Panel A PANEL A (MIN) B (MIN) Upper Front Panel 1625mm 1000mm - - - Side Panel x 2 482mm 1000mm 586mm 138mm 306mm Lower Front Panel 1625mm 138mm - - - Base Panel 1625mm 482mm 1225mm 432mm - Inner Side Panel 200mm 586mm - - - Upper Inner Panel 1625mm 482mm 1225mm 432mm - 28 C D (MIN)
3 SIDED SHADOW GAP CUTTING TEMPLATES Front Panel B A Side Panel x2 B Top B A A PANEL A (MIN) Front Panel WALL MOUNTED 1787mm 1587mm Side Panel x2 Top B (MIN) FLOOR MOUNTED 1000mm 1787mm FLOOR MOUNTED WALL MOUNTED 100mm 509mm 1587mm 509mm 3 SIDED CONSTRUCTION 2 1 4 IMPORTANT: THE BASE PANEL MUST SEAL COMPLETELY TO THE SUPPORTING WALL.
6 3 1 3 If sealing the lower enclosure ensure ventilation is provided NOTE: IT IS NOT NECESSARY TO SEAL THE UPPER ENCLOSURE BACK TO THE SUPPORTING WALL.
SHADOW GAP INSTALLATION 9 12 6 5 13 Minimum: 50mm 10 Minimum: 1075mm Minimum: 1000mm Minimum: 25mm Vertical Overlay Minimum Height: 100mm Top View VENTED INSTALLATION 11 50mm Appliance Enclosure Wall Shadow Gap 31
ENCLOSURE CONSTRUCTION 2 SIDED INSTALLATION Example enclosure VENTILATION Note: If the lower section of the enclosure is sealed (to the floor or capped if designed as a floating shelf) it will be necessary to provide a vent with a free area of 150cm2 on each side. If the upper section is sealed (to the ceiling or capped if designed as a floating shelf) it will be necessary to provide a vent with a free area of 400cm2 on each side.
2 SIDED INSTALLATION CUTTING TEMPLATES A Front Side Panel B Upper Front Panel B B Closed Side Panel (If not installing against a wall) A A Short Side Panel B Lower Front Panel B A A B C Open Side Panel B F Lower Base Panel D E A E D C B F C Upper Inner Panel D A A PANEL E A (MIN) B (MIN) C (MIN) D E F Upper Front Panel 1475mm 1000mm - - - - Open Side Panel 482mm 1000mm 138mm 586mm 304mm - Closed Side Panel (If not installing against a wall) 482mm 1724mm -
2 SIDED SHADOW GAP CUTTING TEMPLATES B A B B A A PANEL Front Panel A (MIN) FLOOR MOUNTED WALL MOUNTED 1687mm 1487mm Side Panel x2 Top B (MIN) 1000mm 1687mm FLOOR MOUNTED WALL MOUNTED 100mm 509mm 1487mm 509mm 2 SIDED CONSTRUCTION 1 2 4 IMPORTANT: THE BASE PANEL MUST SEAL COMPLETELY TO THE SUPPORTING WALL.
3 6 1 3 NOTE: IT IS NOT NECESSARY TO SEAL THE UPPER ENCLOSURE BACK TO THE SUPPORTING WALL.
9 10 12 VENTED INSTALLATION 13 11 SHADOW GAP INSTALLATION 14 36
15 GAS SOUNDNESS PRESSURE CHECK This is a working pressure test and must be carried out with all other gas appliances in the property in operation. Minimum:50mm Connect a suitable pressure gauge to the test point located on the inlet fitting. Turn the gas supply on. Minimum: 1070mm Minimum Height: 100mm Minimum: 1000mm Test Point Minimum: 25mm Vertical Overlay Top View Remove the fixing screws and loosely place the appropriate burners onto the injectors.
3 7 NOTE: Some burners are pre-fitted with Aeration plates. These are non-serviceable and MUST NOT be altered. 4 ARRANGEMENT OF FUEL BED COMPONENTS TAKE CARE NOT TO SPILL THE FUEL EFFECT INTO THE PILOT AREA. ONLY GENUINE GAZCO PARTS CAN BE USED IN THIS APPLIANCE. Use the entire bag of supplied Amber Effect. The Shale Effect is supplied as large pieces which will need to be broken into 2-3 smaller shards before placing onto the fuel bed. It is not necessary to use all the supplied Shale Effect.
2 ASSEMBLING THE FUEL BED G L 6 H G 3 7a G G 4 ≈75 % B L 7b � 8 C 9 5 A 39
14 10 F J 11a 11b 12 M X � 15 16 17 A A 13 M A 40 18 ≈25 %
3 19 Top Support Bracket Gap Bottom Support Bracket Gap NOTE: ENSURE THAT THE LOGS ARE POSITIONED AS ABOVE. ONLY USE THE CORRECT AMOUNT OF LOGS AS SPECIFIED IN THE DIAGRAMS. COMPLETION OF ASSEMBLY 4 1 1 2 5 Top Cam Lock Brackets THE FRONT GLASS SHOULD PRESS FIRMLY AGAINST THE SIDE GLASS. 900 Check the alignment of all the glass panels to ensure the Front Glass and Side Glass all sit flush to one another.
LIGHTING THE APPLIANCE 6 The appliance is operated by thermostatic and programmable remote control. 7 Via the remote it is possible to control the following features: Child proof lock Time Signal Indicator Thermostatic Mode Battery Status Countdown timer Light Program Mode Temperature ENSURE THAT ALL GLASS PANELS ARE FLUSH AND THAT THERE ARE NO GAPS BETWEEN PANELS.
TURNING THE APPLIANCE OFF (STANDBY) Press and hold the Position the Wi-Fi module in the Wi-Fi module bracket. 3 button to turn the appliance off. NOTE: There is a 5 second delay before the next ignition is possible. TROUBLESHOOTING IMPORTANT: In the unlikely event that the handset fails to communicate correctly with the appliance it may be necessary to turn off the gas supply at the isolation valve until any problems can be resolved.
Follow the steps listed in the MyFire App Setup manual PR2467 to connect a smart device to the fire. Replace the Front Glass, Cam Lock Brackets, Glass Support Bracket, and trims. ENSURE THAT THE GLASS BRACKETS ARE SECURE AND IN THE ORIGINAL ORIENTATION. The installation is now complete. Once the Wi-Fi module has been installed and connected to a power source there is a 24 hour window to complete the setup process on the MyFire app.
COMMISSIONING Complete the Commissioning Checklist at the front of this manual covering: — Thermocouple soundness checks. This is to include ensuring the thermocouple is secure on the pilot bracket assembly, lead connection and integrity. — Flue checks REPROGRAMMING HANDSET/ CONTROL BOX To access the control box: Remove the decorative trim, see Servicing Instructions. Access is now possible through the aperture below the centre-left hand side of the appliance using an angled pointed tool.
SERVICING/FAULT FINDING CHARTS SERVICING REQUIREMENTS IMPORTANT – The glass panels on this appliance should be checked for any signs of damage on the front face of the glass panel (scratches, scores, cracks or other surface defects). If damage is observed, the glass panel must be replaced and the appliance must not be used until a replacement is installed. Under no circumstances should the appliance be used if any damage is observed.
FAULT FINDING CHARTS IGNITION FUNCTIONAL CHECK 1 PILOT WILL NOT LIGHT Ensure there is no debris around the pilot assembly, (e.g. soot, etc.) which could short the spark, clean the area. No Yes Operate the valve. Is there a spark? Yes Does the pilot light? No Consult User Instructions and retry.
Replace the combined lead and piezo, retry. No Is the electrode wire detached from the piezo in the valve? No Replace the electrode. Yes Yes No No Correct and retry. Reset the pilot burner. Is the control system being operated correctly? Yes Yes Replace the piezo and gas valve and retry. No Remove the electrode lead from the piezo. Operate the valve. Does a spark jump from the piezo to the valve body? Check for defective or damaged control knob spindle or cam operation.
GENERAL All main components can be replaced without removing the appliance from its installation. Loose the front glass clamps. 3 Top Pivot Brackets DISCONNECT MAINS ELECTRICAL SUPPLY AT THE ACCESSIBLE PLUG OR DEDICATED SWITCH BEFORE SERVICING THE APPLIANCE. IT IS ESSENTIAL THAT THE GAS SUPPLY TO THE APPLIANCE IS TURNED OFF AT THE ISOLATION DEVICE BEFORE PROCEEDING FURTHER.
Loosen and slide side glass bracket. To replace the glass panel, replace in reverse order. Ensure that the brackets engage with the glass panel and the glass is pressed firmly into position. 7 ENSURE THAT ALL GLASS PANELS ARE FLUSH AND THAT THERE ARE NO GAPS BETWEEN PANELS. 2 1 UNDER NO CIRCUMSTANCES SHOULD THE APPLIANCE BE USED IF ANY OF THE GLASS PANELS ARE LOOSE, DAMAGED, OR MISSING. Replace the lower and side trim. REMOVING THE FUEL EFFECT Repeat for the 2 upper Brackets and 2 lower Brackets.
REMOVING THE LOG BURNERS AND MAIN CONTROL ASSEMBLY 5 Remove the Front Glass. Remove the Fuel Effect. 1 6 2 4 2 1 3 Turn the gas supply off at the isolation device. HAVE YOU ISOLATED THE GAS SUPPLY? Disconnect the isolating device from the appliance inlet pipe (A) to isolate the gas supply. 3 4 7 Remove the remaining screws securing the Main Control Assembly to the firebox. 8 WHEN REPLACING THE MESH TRAY TAKE CARE NOT TO DAMAGE THE LOG BURNER BRACKETS, PILOT AND CROSS LIGHTER.
13 9 10 14 1 2 Disconnect the Mains Lead Plug, the LED leads and the receiver lead from the Module and the Wi-Fi box (if installed). DO NOT REMOVE THE WIRES FROM THE PLUG. NOTE: Take care not to catch any loose wiring previously disconnected against the front edge of the firebox. Replace in reverse order. 11 AFTER SERVICING ENSURE THAT ALL CONNECTIONS ARE REPLACED BEFORE REPLACING THE MESH TRAY. Module wires REPLACING THE LED CIRCUIT There are 5 LED boards, which can be replaced individually.
THE LED'S ARE FRAGILE. HANDLE WITH CARE. ONLY HOLD THE LED BOARDS BY THE EDGES TO AVOID CONTACT WITH THE TOP OF THE LED'S. 5 2 AVOID CATCHING ANY DELICATE WIRES WHEN REPLACING THE SCREWS. 1 Remove the Log Burners, Fuel effect, and Mesh tray. 1 The LED circuit consists of three components, which can be individually changed, these are: Front LED Boards. Rear LED Bar. Driver.
2 PILOT UNIT ASSEMBLY Turn off the gas supply at the isolating device. Remove the Log Burners and Main Control Assembly. The pilot bracket can be accessed from the underside of the Main Control Assembly. IMPORTANT: UNDER THE TERMS OF THE EXTENDED WARRANTY IT WILL BE COMPULSORY TO CHANGE THE COMPLETE PILOT UNIT ON THIS APPLIANCE IN YEARS 2 AND 4. Disconnect the LED Mains Lead Plug from the Module. Undo pilot pipe from the control valve, see Arrow A.
ELECTRODE GAS VALVE Pull the ignition lead off the electrode and undo the retaining nut, see arrow A. 3 To change the gas valve: Remove the Log Burners and Main Control Assembly. Disconnect the Gas Inlet Pipe, Arrow A. Disconnect the Gas Outlet Pipe, Arrow B. Disconnect the Pilot Pipe, Arrow C. C Disconnect the Thermocouple, Thermocurrent Wires and the Interrupter Block, Arrow D. Remove the Eight Wire Loom, Arrow E. A B There is an access hole abovce the cable plug oin the valve.
After replacing the Control Box ensure that all cable ties and connections are refitted. CONTROL BOX To replace the Control Box first remove the Main Control Assembly. Cut the cable tie holding the Ignition lead and the Thermocurrent cables. After replacing the Control Box you will need to reprogram the handset. — Press and hold the reset button on the control box until you hear two signals. After the second longer signal: Disconnect the Module and Solenoid leads from the Control Box.
Undo the Injectors individually. Turn the Main Control Assembly over. Withdraw the Cross Lighting bar from the Control Assembly. The Injector is screwed into the bottom of the bar. 3 3 Replace with the correct size Injector. See table on Page 12. NOTE: DO NOT OVERTIGHTEN. Use thread sealant Loctite 572 when replacing Injectors. Repeat for the remaining Injectors. Check for leaks. CROSS LIGHTING INJECTOR Replace with the correct size Injector and refit all components in the reverse order.
Remove the Solenoid plug from the Control Box, Arrow A. BACK PANEL Cut the cable tie. NOTE the orientation of the cables. 3 Replace in reverse order. Check for leaks. Ensure that the cable ties are replaced. CHANGING BETWEEN GAS TYPES In order to change between gas types it will be necessary to change both the burner assembly and the complete control assembly. Contact your Gazco retailer for further information. A kit of parts is available for this.
SIDE GLASS PANELS BAFFLE Remove the Front Glass, Fuel Effect, and Main burners. THE SIDE GLASS DOES NOT NEED TO BE REMOVED TO SERVICE THE APPLIANCE. Remove the Rear Liner and Side Liner (if applicable). It is recommended to leave the Side Glass in situ unless absolutely necessary. The Baffle is held in position by 10 screws. 1 CONVERTING FROM 3 TO 2 SIDES 1 Underside of Baffle Front of appliance 2 2 Replace in reverse order. Loose the front glass clamps.
4 62 8 Upper Side Brackets Lower Side Brackets 5 Top Support Bracket With the brackets disengaged, carefully slide the side glass panel forward, lift, and swing the bottom out to remove. Place the glass carefully to one side. 9 Gap Bottom Support Bracket 1. Gap 2. 3. Lift out the front glass. 6 Fully remove the side bracket. 1 10 2 Loosen and slide side glass bracket. 7 Fit the side panel. 1 Repeat for the 2 upper Brackets and 2 lower Brackets.
Refit the front glass. 11 15 Attach the top and bottom side brackets. 12 Refit one of the decorative side trims and new base trim. 16 Fit the decorative trim. To Replace: 13 Place the Side Glass panel in position. Do not tighten the brackets at this stage. Replace the Front Glass Panel and tighten the front brackets, ensuring the Side Glass sits on the spring clip located in the rear channel. Push the rear side brackets up against the side glass and tighten the screws.
REPLACING THE POWER CABLE 4 BEFORE UNDERTAKING ANY WORK SWITCH OFF THE APPLIANCE AND ISOLATE THE POWER SUPPLY ENSURING THERE IS NO POWER TO THE APPLIANCE. 1 5 Top Support Bracket Gap Bottom Support Bracket Gap 2 Lift out the front glass. 6 1 Loose the front glass clamps.
Loosen the locking screw securing the Power Cable in place. 8 12 Disconnect the LED Mains Lead Plug from the Module. 9 Inside View Withdraw the old cable. Module wires Fit the new cable in reverse order ensuring it is rewired in the original configuration. LED wires Disconnect the LED plug and Mains lead from the module. 10 Mains Lead Module Lead LED Plug Disconnect the 3 cables from the Power Module, Arrow A. NOTE THE CONFIGURATION OF THE WIRES.
SPARE PARTS - MAIN ASSEMBLY PART CODE PART CODE NO. COMPONENT NATURAL GAS LPG QTY. NO. COMPONENT NATURAL GAS LPG QTY.
REFLEX 105 CONTROL ASSEMBLY PART CODE PART CODE NO. COMPONENT NATURAL GAS LPG QTY. NO. COMPONENT NATURAL GAS LPG IN0054 IN0109 QTY.
Reflex 105 Multi-sided BF NG Reflex 105 Multi-sided BF LPG 130 130 Nominal Heat Output - Pnom 10.0kW 11.1kW Minimum Heat Output (indicative) -Pmin 4.4kW 4.2kW Auxiliary Electricity Consumption At Nominal Heat Output - elmax 0.003kW 0.003kW At Minimum Heat Output - elmin 0.003kW 0.003kW In Standby Mode - elsb 0.003kW 0.003kW Useful Efficiency (NCV) INFORMATION REQUIREMENT FOR GASEOUS FUEL LOCAL SPACE HEATER Useful Efficiency at nominal heat output - ηth,nom 89.0% 89.
SERVICE RECORDS 1ST SERVICE 2ND SERVICE - PILOT CHANGE REQUIRED Date of Service:.......................................................................... Date of Service:.......................................................................... Next Service Due:...................................................................... Next Service Due:...................................................................... Signed:.............................................................................
Gazco Ltd, Osprey Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7JG Tel: (01392) 474011 Fax: (01392) 219932 E-mail: info@gazco.com www.gazco.