Sales Guide

ZVAC Hydronic Kit Specifications
RAVHW1 RAVHW2 RAVHW3
Performance specifications for hydronic heating kits applied to AZ75W-series ZVAC models: The ZVAC hydronic heat kits are matched up (applied) to the AZ75W-series models as shown below:
RAVHW1 (1-Row Kit) RAVHW2 (2-Row Kit) RAVHW3 (3-Row Kit)
ZVAC cool-only PTAC model—matched to hydronic kit as shown
AZ75W09DAC AZ75W12DAC AZ75W09DAC AZ75W12DAC AZ75W18DAC AZ75W12DAC AZ75W18DAC
Voltage (60 Hertz) 230/208 230/208 230/208 230/208 230/208 230/208 230/208
Heating capacity designed to meet standard ARI rating
conditions of 200°F water entering temp/180°F water exiting
temp/70°F entering air temp 17,300/16,200 20,200/19,100 25,900/23,500 2 9, 40 0/27, 60 0 34,700/32,900 33,200/31,100 39,600/37,300
External static pressure 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" (Max.) 0.25" (Max.)
Air flow (SCFM) 297/256 385/344 297/256 364/328 470/430 362/330 467/426
Water flow rate (GPM) 1.8/1.7 2.1/2.0 2.7/2.4 3.0/2.8 3.5/3.3 3.4/3.2 4.1/3.8
Water press drop* (ft. of water) 2.7/2.4 3.6/3/3 3.7/3.1 5.0/4.3 6.7/6.0 6.5/5.7 9.2 /7. 9
Face velocity (ft./min.) 238/205 308/275 238/205 291/262 376/262 290/264 374/341
Heat exchanger fin height (in.) 12 12 12 12 12 12 12
Heat exchanger finned length (in.) 15 15 15 15 15 15 15
Heat exchanger – fin per inch 11 11 11 11 11 10 10
Heat exchanger – fin material Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum
Weight/Dimensions for hydronic kits:
Hydronic heat kit model # RAVHW1 RAVHW2 RAVHW3
Hydronic heat kit height, inches 13-5/8 13-5/8 13-5/8
Hydronic heat kit width, inches 19 19 19
Hydronic heat kit depth, inches 22 22 22
Shipping weight, pounds 32 35 38
Net weight, pounds 27 30 33
32 1/4" H
For GE appliance service in the U.S., call
1-800-GE CARES. In Canada, call 1-888-209-0999.
GE has a policy of continuous improvement of
its products and reserves the right to change
materials and specifications without notice.
© 2009 GE Company
Pub. No. 20-S099 PC58439
Vertical Zoneline
®
warranty
*
What is covered
Limited one-year warranty
One year from the date of the original purchase, GE will replace any part
of the air conditioner which fails due to a defect in materials or work-
manship. During this limited one-year warranty, GE will provide, free of
charge, all labor and related service costs to replace the defective part.
Limited five-year warranty
Five years from the date of the original purchase, GE will replace Sealed
Refrigerating System, if any part of the Sealed Refrigerating System (the
compressor, condenser, evaporator, and all connecting tubing) should
fail due to a defect in materials or workmanship. During this limited
five-year warranty, GE will provide, free of charge, all labor and related
service costs to replace the defective part.
Specifications
Limited second through fifth year parts warranty
For the second through the fifth year from the date of the original
purchase, GE will replace Fan Motors, Switches, Heater, Heater
Protectors, Compressor Overload, Solenoids, Circuit Boards, Auxiliary
Controls, Thermistors, Frost Controls, ICR Pump, Capacitors, Varistors and
Indoor Blower Bearing, if any of these parts should fail due to a defect
in materials or workmanship. During this additional four-year limited
warranty, you will be responsible for any labor and related service costs.
*See written warranty for details
GE Consumer & Industrial
Appliances
General Electric Company
Louisville, KY 40225
geappliances.com
AZ75E09DAC AZ75E12DAC AZ75E18DAC AZ75H09DAC AZ75H12DAC AZ75H18DAC
Electric resistance heat Heat pumps
Features
BTUH 9,500/9,300 11,700/11,500 17, 50 0/17, 20 0 9,500/9,300 11,700/11,500 17, 50 0/17, 20 0
E.E.R. (BTUH/Watt) 10.5/10.5 10.7/10.7 10.0/10.0 10.5/10.5 10.7/10.7 10.0/10.0
Dehumidification (pints/hr.) 2.7 3.6 5.0 2.7 3.6 5.0
Universal Heater (kW) 2.55/3.45/5.0 2.55/3.45/5.0 2.55/3.45/5.0 2.55/3.45/5.0 2.55/3.45/5.0 2.55/3.45/5.0
Heating Cap (BTUH) 8,400/8,200 10,900/10,700 15,700/15,500
COP @ 47° 3.6 3.3 3.1
Voltage (V) 230/208 230/208 230/208 230/208 230/208 230/208
Unit Width (in.) 23-1 /8 23-1 /8 23-1 /8 23-1 /8 23-1 /8 23 -1/8
Unit Depth (in.) 23-1 /8 23-1 /8 23-1 /8 23-1 /8 23-1 /8 23 -1/8
Unit Height (in.) 32-1 /4 32-1 /4 32-1 /4 32-1/4 32-1/4 32-1/4
Indoor CFM (Hi/Med/Low) 310/260/230 375/315/250 550/475/440 310/260/230 375/315/250 550/475/440
23 1/8" W
23 1/8" D
Overall Unit Dimensions
geappliances.com