Architect and Engineering Manual

geappliances.com
25
Preliminary specifications are subject to change
GE APPLIANCES VERTICAL ZONELINE HEAT PUMPS
ADDITIONAL SPECIFICATIONS
Heat pump unit shall automatically switch from heat pump operation to electric resistance heat
when it is unable to provide sufficient heat to maintain room temperature or when the outdoor
temperature is 25
o
F or less.
In the event of a compressor failure during heat pump operation, the unit shall automatically
switch to electric resistance heat to maintain selected room temperature regardless of outdoor
temperatures.
Unit shall have an indoor coil temperature sensor to protect the compressor when the outdoor
temperatures are too high for heat pump operation.
ADDITIONAL SPECIFICATIONS SERVICE
Submit complete information with bid covering service availability, to whom
service on units will be assigned, complete address and phone number,
including phone number of emergency service personnel.
STARTUP, ADJUST, DEMONSTRATE
Contractor shall be responsible for the initial starting of units, adjustments
thereto, cleaning, etc., to place the units in required operating condition.
Contractor shall demonstrate to the owner, or his representative, the operation
of units for both summer and winter functions.