UNIT AND INSTALLATION NOTES
The unit is a one-piece package system that fits
directly into a closet enclosure. Once the drain platform
(RAVDPLAT) has been installed, the chassis can be
positioned on the drain platform and pushed towards
the exterior wall. The chassis will drop down slightly
into the platform, securing it in place and engaging
the gasket on the wall plenum (RAVWPT15). Power,
thermostat, and duct connections can then be made.
A 10" diameter flange on the top of the unit is used to
connect to field-supplied, insulated, flexible or rigid
transition duct with an adjustable ring clamp.
Flexible duct may be used for transitions only. Rigid
duct must be used for 90-degree bends and tees.
Do not use flexible duct for unsupported runs of five
feet or more.
POWER CONNECTION KIT
All AZ95 Series Vertical Units are equipped with
universal heaters that are capable of different heater
outputs. Heater output is determined by which unique
direct connect power kit is being used. This increases
the flexibility of a chassis where various heating
requirements may need to be met at a site. This power
connection is the only means of supplying power to the
AZ95 chassis. Please reference the chart on page 5 to
determine the appropriate power connection kit for
your project.
RETURN AIR GRILLE, ACCESS PANEL
OR LOUVERED CLOSET DOOR
The return air from the room to the unit may enter the
closet through one of four ways.
A louvered door may be installed on the closet to allow
return air to enter. When a louvered door is used, the
filter would be installed in the filter bracket on the front
panel of the unit.
A wall-mounted access panel may be used instead of a
louvered door. The return air is through the access panel,
model RAVRG4, which requires a 28 1/8" W x 55 7/8" H
cutout in the wall, and there is a filter bracket behind the
grille louvers.
A return air grille, model RAVRG2, may also be used
and is designed to be installed in a 20-3/8" by 20-3/8"
cutout in a flush closet door or closet sidewall. In
this installation, a filter can fit into the bracket in the
RAVRG2.
A field-supplied return air grille, with a minimum
dimension of 20" W x 20" H, may be used if mounted
in a cutout in the door or wall. When employing this
method for return air, the filter is installed in the bracket
mounted on the unit.