Installation Instructions
Table Of Contents
31-7000092 Rev. 1 3
Installation Instructions
HOOD EXHAUST
The following chart describes an example of one possible 
ductwork installation.
NOTE: Read these next two pages only if you plan to vent your exhaust to the outside. If you plan to recirculate the air back 
into the room, proceed to page 11.
OUTSIDE TOP EXHAUST (EXAMPLE ONLY)
NOTE: For back exhaust, care should be taken to align exhaust with space between studs, or wall 
should be prepared at the time it is constructed by leaving enough space between the wall studs to 
accommodate exhaust.
*   IMPORTANT: If a rectangular-to-round transition adaptor is used, the bottom corners of the damper  
will have to be cut to fit, using the tin snips, in order to allow free movement of the damper.
The following chart describes an example of one possible 
ductwork installation.
OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
 EQUIVALENT   NUMBER     
DUCT PIECES
 LENGTH  x USED  =  LENGTH 
      Roof Cap    24 Ft.    x  (1)    =  24 Ft.   
      12 Ft. Straight Duct  12 Ft.    x  (1)    =  12 Ft.     
   (6″Round)
   Rectangular-to-Round 5 Ft.  x (1)  = 5 Ft.  
      Transition Adaptor* 
Equivalent lengths of duct pieces are based on actual tests and  
reflect requirements for good venting performance with any vent hood.
  Total Length  =  41 Ft.
 EQUIVALENT   NUMBER   
DUCT PIECES    LENGTH*  x  USED    = LENGTH 
      Wall Cap    40 Ft.    x  (1)    =  40 Ft. 
      3 Ft. Straight Duct  3 Ft.    x  (1)    =  3 Ft.   
(3
1
⁄4″x10″Rectangular)
   90° Elbow  10 Ft.  x (2)  = 20 Ft.  
Equivalent lengths of duct pieces are based on actual tests and  
reflect requirements for good venting performance with any vent hood. 
 Total Length  =  63 Ft.










