16V PicoTLynx
TM
4A: Non-Isolated DC-DC Power Modules
8Vdc –16Vdc input; 0.6Vdc to 8.0Vdc output; 4A Output Current
September 10, 2013 ©2013 General Electric Company. All rights reserved. Page 2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only,
functional operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of
the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter Device Symbol Min Max Unit
Input Voltage All V
IN
-0.3 18 Vdc
Up to 10 seconds
Operating Ambient Temperature All T
A
-40 85 °C
(see Thermal Considerations section)
Storage Temperature All T
stg
-55 125 °C
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.
Parameter Device Symbol Min Typ Max Unit
Operating Input Voltage All V
IN
8.0
16.0 Vdc
Maximum Input Current All I
IN,max
6.5 Adc
(V
IN
=8V to 16V, I
O
=I
O, max
)
Input No Load Current
(V
IN
= 16.0Vdc, I
O
= 0, module enabled)
V
O,set
= 0.6 Vdc I
IN,No load
18 mA
V
O,set
= 8.0Vdc I
IN,No load
96.1 mA
Input Stand-by Current
(V
IN
= 16.0Vdc, module disabled)
All I
IN,stand-by
1.2 mA
Inrush Transient All I
2
t 1 A
2
s
Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 1μH source impedance; V
IN
=0 to 16V
,
I
O
= I
Omax
; See Test Configurations)
All 50 mAp-p
Input Ripple Rejection (120Hz) All -46 dB
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This power module can be used in a wide variety of applications, ranging from simple standalone operation to an integrated part of
sophisticated power architecture. To preserve maximum flexibility, internal fusing is not included; however, to achieve maximum safety
and system protection, always use an input line fuse. The safety agencies require a fast-acting fuse with a maximum rating of 6 A (see
Safety Considerations section). Based on the information provided in this data sheet on inrush energy and maximum dc input current, the
same type of fuse with a lower rating can be used. Refer to the fuse manufacturer’s data sheet for further information.