g DEH41080 Rev.
Table of Contents Product Description ............................................................................................................3 Product Specifications ........................................................................................................3 Power Requirements ...........................................................................................................................................................3 Ambient Ratings ...........................................
NET1 – Main LAN (BACnet MS/TP) • BACnet MS/TP Communications Speed @ 9,600, 19,200, 38,400, or 76,800 bps; default 76,800 bps • MODBUS Communications Speed @ 9,600, 19,200, or 38,400; default @ 9600 bps • Maximum of 99 nodes per MS/TP segment (50 without a repeater) Product Description The A Series ® Lighting Controller (cat. no. 10092046P2) is a fully programmable Native BACnet/MODBUS System Controller. Standard communications ports are RS-232 and RS-485, with an Ethernet option.
Physical Parameters • Size – 10.765" x 6.070" x 2" (27.3 x 14.6 x 5.1 cm) • Weight – 1 lb (454 gm) Hardware Overview Configuration • 16-bit Processor • 2 MB(16Mbit) flash memory (software loadable firmware) • 512 kB SRAM memory (for database) • Database backup via nonvolatile flash memory • Real-time clock with lithium battery for clock and SRAM backup • Visual LED status indication of the CPU Figure 1. Three-wire maintained connections.
Indicators The LED indicators on the lighting controller and their functions are listed in Table 2. LED Network (Ethernet) Power Scan Network (NET1) Network (NET2) Alarm Output (BO68) Function Description One LED (LNK) turns on to indicate a cable link is successfully Ethernet Communication Status established, and another green LED (ACT) flashes to indicate Indicators LNK and ACT network activity (incoming or outgoing data) on the port. This amber LED is lit when control power is present on the device.
representing the network level that it will reside on in the network architecture (area, system, subnet). Other than the one device acting as a router/gateway, all other devices on the same network segment must be configured the same way. BACnet network.
Termination boards. A termination board should be installed at both ends of each MS/TP network segment, or two per MS/TP or LINKnet network.
Default Database Breakers The lighting controller supports 12-, 18-, 24-, 30-, 36-, and 42-circuit panels. Binary outputs (BO) are mapped to the possible physical outputs of the lighting controller. Each binary output has a breaker-override binary variable (BV) referenced as the override input field, with a default override time of 120 minutes. Commanding the breaker override BV from O F F to ON triggers the override condition for the given binary output.
Description Light Switch Inputs GE-1600i Light Switch Inputs (1st GE-1600R) Light Switch Inputs (2nd GE-1600R) Light Switch Inputs (3rd GE-1600R) Light Switch Inputs (4th GE-1600R) Light Switch State Text/Configuration Type RO RO RO RO RO BACNet Object MI101-116 MI201-216 MI301-316 MI401-416 MI501-502 MIC1 Modbus Register Fn 4, 01 – 16 Fn 4, 17 – 32 Fn 4, 33 – 48 Fn 4, 49 – 64 Fn 4, 65 – 66 * * MIC selected with the LCD Programmer. Table 6.
Up to eight ON/OFF intervals per day for each day of the week and two Calendar references can be entered into Schedule (SCH) objects. When day-of-the-week and entered ON time equal that of the controllers, the Schedule object transitions from OFF to ON. When a Calendar is referenced to a Schedule object and the Calendar is ON, the Schedule will only execute the Calendar ON/OFF times. Schedule objects are listed in Table 10.
Alarm Relay Load Shedding The Compact Event Log (CEL) has control of the Alarm Output (BO68). The alarm values in the Alarm Output tab classify what events will trigger the Alarm Output. The enabling Device Statuses alarm when a reset, dead battery, device offline, or undervoltage event occurs. Time Change alarms when a Time Change event occurs. Lighting Statuses alarm when a Status On or a Status Off event occurs. Lighting Alarms alarm when a Command Failure, or a Breaker Tripped event occurs.