O-14 Configurable Control Word CTW
Option: Function:
Selection of control word bit 10 if it is active low or active high
[0] None
[1] * Profile default
[2] CTW Valid, active low
O-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the network.
[0] Digit Input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or network option module.
[2] Logic AND Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the network.
Option: Function:
[0] Digital Input
[1] Bus
[2] Logic AND
[3] * Logic OR
NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.
O-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the network.
[0] Digit Input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or network option module.
[2] Logic AND Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.
OPCEIP EtherNet/IP