Figure 6. Close Coil wire routing
Installation of Electrical close switch:
10. Slide the switch assembly over the
mechanism side sheet and locate in the two
locating holes as shown in Fig. 7.
Figure 7. EC switch assembly
11. Assemble the screw with washer as shown in
Fig. 8. Tighten the screw to torque 1.2N-m (0.9 ft-
lbs).
Figure 8. Screw assembly
12. Plug the connector from the EC switch
assembly to the connector from the command
closing coil beside the PMU base as shown in
Fig 9.
Figure 9. Connector plug assembly
Installation of Push button on the fascia:
13. Remove the existing dummy button by
removing the screw as shown in fig 10.
Dummy button
Screw
Figure 10. Connector plug assembly