obj,attr
description
sta
cha
ope
type
Range of Values
dc1,ide
Description
text
DC1
dc1,des
Description
text
DC Plant 1
dc1,typ
Plant Type
number
48V, 24V
dc1,vdc
Plant voltage
number
dd.dd V
dc1,adc
Plant load current
number
ddd.d A
dc1,cap
Total installed rectifier capacity
number
ddd.d A
dc1,olcap
Total on-line rectifier capacity
number
ddd.d A
dc1,trd
Plant total rectifier drain
number
ddd.d A
dc1,sht
Centralized plant shunt type
Text
“NONE”, ”BATTERY”,
”LOAD”
dc1,sha
Centralized plant shunt size
Number
0=disabled 1-9999
dc1,stt
Plant state
text
“FLOAT”, “BOOST”
dc1,bod
Battery on discharge
number
0=on discharge 1=not on
discharge
dc1,ems
Efficiency state
number
0=inactive 1=active
dc1,eme
Efficiency enable
number
0=disable 1=enable
dc1,emt
Efficiency target
number
20% to 95% of rectifier
capacity
dc1,emo
Efficiency rectifier turn on
threshold
number
25% to 100% of rectifier
capacity
dc1,rss
Rectifier restart
number
0=no action 1=restart
dc1,rsq
Rectifier sequencing
number
0=disable 1=enable
dc1,ron
User Group TR request
Number
0-3 LSB = User, MSB=PBT
dc1,rot
All Rectifier On Threshold
number
20-25or 40-50 volts
dc1,nst
Number of battery strings
number
1-70
dc1,cps
Number of Cells per String
number
1-75 (24V plant) or 24 (48V
plant)
dc1,bty
Battery type
Text
See battery type definitions
default (OPE causes battery
defaults to be loaded)
dc1,isd
Imminent shutdown enable
number
0=disable 1=enable
dc1,rtm
Actual reserve time
text
Low Current-Batt current too
low
High Current-
Batt current
too high
dd.d (in hours)
dc1,scap
String capacity
number
dc1,mls
All load shunts monitored
number
0=disable 1=enable
DTA-Alarms With Two Thresholds
Related
Command
obj,attr
Description
sta
cha
ope
type
Range of Values
objid,ide
Identifier
text
see below
objid,des
Description
text
see below
objid,fds
Front Panel Description
text
see below
objid,ast
Alarm state
number
0=not active 1=active
objid,led
LED
text
BD,AC,DC,””
objid,sev
Alarm severity
text
CRIT, MAJ, MIN, WRN,
RO