DTA-Alarms With Two Thresholds
Related
Command
obj,attr
Description
sta
cha
ope
type
Range of Values
objid,fth
Alarm boost threshold
number
see below
objid,bth
Alarm float threshold
number
see below
objid,acc
Contact Closure
text
R1,R2,R3,R4,R5,R6,R7,””
objid,dly
Notify Delay
number
0-540 seconds
objid,noo
Notify On Occur
number
0=no 1=yes
objid,nor
Notify On Retire
number
0=no 1=yes
objid,nag
NAG On Occur
number
0=no 1=yes
objid,dst
Notify Destination
text
“”, P1, P2, P3, P4, E1, E2,
E3, E4, S1, S2, S3, S4
objid
Description
Float Threshold
Boost Threshold
bda1
Battery On Discharge
23-28 V
or 46-55 V
23-28 V
or 46-55 V
hfv1
High voltage
24.75-29.75 V
or 50-60 V
25.75-31.75 V
or 52-60 V
hva1
Very high voltage
24.75-29.75 V
or 50-60 V
25.75-31.75 V
or 52-60 V
THA-Alarms With One Threshold
Related
Command
obj,attr
Description
sta
cha
ope
type
Range of Values
objid,ide
Identifier
text
see below
objid,des
Description
text
see below
objid,fds
Front Panel Description
text
see below
objid,ast
Alarm state
number
0=not active 1=active
objid,sev
Alarm severity
text
CRIT, MAJ, MIN, WRN,
RO
objid,thr
Alarm threshold
number
number
objid,led
LED
text
BD,AC,DC,””
objid,acc
Contact Closure
text
R1,R2,R3,R4,R5,R6,R7,””
objid,dly
Notify Delay
number
0-540 seconds
objid,noo
Notify On Occur
number
0=no 1=yes
objid,nor
Notify On Retire
number
0=no 1=yes
objid,nag
NAG On Occur
number
0=no 1=yes
objid,dst
Notify Destination
text
“”, P1, P2, P3, P4, E1, E2,
E3, E4, S1, S2, S3, S4
objid
Description
Threshold
amth1
High ambient temp
30-75C
amtl1
Low ambient temp
-40-10C
btha1
High battery temperature
30-85C
Btla1
Low Battery Temperature
-40C to 10C
Btvh1
Very High Battery Temperature
30C to 85C
Btvl1
Very Low Battery Temperature
-40C to 10C
macf1
Multiple AC Fail
2-88
mrfa1
Multiple Rectifier Fail
2-88
mman1
Multiple Manual Off
2-88