Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 149
objid
Description
Threshold
rrtl1
Real-time reserve low
0-100hrs
rtl1
Reserve time low
0-100hrs
rls1
Redundancy Loss
1-87
vla1
Very low voltage
20-25.5 V
or 40-51 V
SDA- Alarms With No Threshold
Related
Command
obj,attr
Description
sta
cha
ope
type
Range of Values
objid,ide
Identifier
text
see below
objid,des
Description
text
see below
objid,fds
Front Panel Description
text
see below
objid,ast
Alarm state
number
0=not active 1=active
objid,sev
Alarm severity
text
CRIT, MAJ, MIN, WRN,
RO
objid,led
LED
text
BD,AC,DC,””
objid,acc
Contact Closure
text
R1,R2,R3,R4,R5,R6,R7,””
objid,dly
Notify Delay
number
0-540 seconds
objid,noo
Notify On Occur
number
0=no 1=yes
objid,nor
Notify On Retire
number
0=no 1=yes
objid,nag
NAG On Occur
number
0=no 1=yes
objid,dst
Notify Destination
text
“”, P1, P2, P3, P4, E1, E2,
E3, E4, S1, S2, S3, S4
obj
Description
AAC1
ACO Active
ACF1
AC Fail
AMJ1
Auxiliary Major
ATA1
Alarm Test Active
ATB1
Alarm Test Aborted
AUX1
Air Conditioner Fail
AUX2
Door Open
AUX3
High External Ambient
AUX4
Low External Ambient
AUX5
Fan Fail
AUX6
Hydrogen present
BBL1
Real Time Clock Battery Low
BFA1
Battery Test Failed
BTA1
Battery Test Active
CCH1
Configuration Changed
CLC1
Clock Changed
CLM1
Rectifier Current Limit
CMA1
Minor Communication Fail Alarm
CNF1
LVBD 1 Failed
CNF2
LVLD 1 Failed
CNF3
LVLD 2 Failed
CNF4
LVLD 3 Failed
CNO1
LVBD 1 Open
CNO2
LVLD 1 Open
CNO3
LVLD 2 Open