Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 152
csr,adc
DC Current
Number
Number in amps
csr,cap
Capacity
Number
Number in amps
csr,stt
State
Text
ON*, OFF, STANDBY*,
MISSING, VACANT*
ON qualifiers LIM
OFF qualifiers LVD, -INF,
-TA, -HVSD, -FAN
csr,cfa
Converter Fail
Number
0=inactive 1=active
csr,did
ID Conflict
Number
0=inactive 1=active
csr,ccf
Communication Fail
Number
0=inactive 1=active
s stands for shelf number (0 or 1)
r stands for converter number (1 thru 6)
* The user may only set the state to ON, STANDBY, or VACANT
BAR-Battery Reserve Management
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
br1,des
Description
Text
Battery Reserve 1
br1,adc
Total battery current
number
d A (+ for discharge, - for
charge)
br1,hbt
Highest battery temperature
number
dd
°
C
br1,lbt
Lowest battery temperature
number
dd
°
C
br1,cap
Installed battery capacity
number
ddddd AH
br1,olcap
On-line battery capacity
number
ddddd AH
br1,btr
Discharge test results
text
result,reserve,load
result is one of the following:
COMPLETED
CHECK BATTERY
INTERRUPTED
ACTIVE
NOT RUN
reserve is hours calculate by
last complete test
load is load at beginning of
test
br1,tth
High Temperature Threshold
Number
30-90
°
C or 86-194
°
C
br1,cle
Current Limit Enable
number
0=disable 1=enable
br1,clt
Current Limit Threshold
number
5-1000A
br1,cev
Battery string end of discharge V
Number
19.25-22.75V
or 40.25-43.75V
br1,bts
Battery Test State
number
0=inactive 1=active
br1,mtt
Manual test type
text
DISABLED, 20%, TIMED
br1,tev
Manual test alarm voltage
number
21-27V or 36-48 V
br1,tmd
Manual test duration
number
0.1-99.9 hours
br1,bte
Auto test type
text
DISABLED, 20%, TIMED
br1,btv
Battery test rectifier voltage
number
21-26 V or 42-52 V
br1,ath
Auto test start hour
number
0-23
br1,tin
Auto test interval
number
1-18 months
br1,atw
Auto test min hours after BD
number
0-240 hours
br1,atd
Auto test date
date
dd-mmm-yy
br1,nvm
Number of mid-cell V present
d