BAR-Battery Reserve Management
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
br1,ntm
Number of temperatures present
d
br1,scd
Battery voltage imbalance
detection enable
number
0=disable,1=enable
(Automatically enabled when
mid cell V monitor present)
br1,scv
Battery imbalance threshold
number
1.5-3.0V
BTD- Battery Type Definition
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
btnn,des
Description
Text
Battery Configuration 1
btnn,bty
Battery Type
Text
Up to 14 characters
btnn,btc
Battery Class
Text
FLOODED, SEALED,
NICD, LI_LMP, LI_ELITE
btnn,cap
Capacity
Number
number
Where n stands for battery type number (1 thru 25)
BST- Boost Management
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
bs1,ide
Identifier
Text
BS1
bs1,des
Description
Text
Boost Control 1
bs1,stt
State
Text
QRCT, MANUAL, BTP,
TIMED AU-TO, OFF
bs1,atm
Auto Mode
Text
OFF, QRCT, TIMED
bs1,tmd
Timed Manual Duration
Number
1-80 hours
bs1,amf
Auto Multiplication Factor
Number
0.1-9
bs1,cta
Current Term Current Thresh
Number
1-999A
CNT- Disconnect Contactor Control
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
cnx,ide
Identifier
number
CN1, CN2, CN3, CN4
cnx,des
Description
number
Contactor 1
cnx,stt
Status
text
NONE, DISCON,
CONNECT, FAILED
cnx,ena
Control enable
0=disable,1=enable
cnx,dth
Disconnect threshold
Vmin in adaptive mode
number
39V to 50V
cnx,dvx
Vmax in adaptive mode
number
39V to 50V
cnx,din
Imin in adaptive mode
number
0A to 9999A
cnx,dix
Imax in adaptive mode
number
0A to 9999A
cnx,ddy
Disconnect maximum delay
time
00:00:00 to 04:59:59
cnx,ddy
Disconnect delay
number
0-300 minutes
cnx,dam
Disconnect automode
text
0=“NONE”
1=“VOLTAGE”