Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 154
CNT- Disconnect Contactor Control
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
2= “VOLTAGE+TIME”
cnx,dtm
Disconnect remaining time
number
>0 means going to
disconnect
cnx,rth
Reconnect threshold
number
19.5-27V or 39-55V
cnx,rdy
Reconnect delay
number
0-300 seconds
cnx,ram
Reconnect automode
text
0=“NONE”
1=“VOLTAGE”
2=“VOLTAGE+TIME”
cnx 4,rtm
Reconnect remaining time
number
>0 means going to reconnect
The contactors are identified as follows:
CN1 = Battery Disconnect (LVBD1)
CN2 = Load 1 Disconnect (LVLD1)
CN3 = Load 2 Disconnect (LVLD2)
CN4 = Load 3 Disconnect (LVLD3)
DCM- Distribution Current Monitor
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
dcmxx,ide
Identifier
number
DCMC1 is the plant shunt
DCM01-DCM08
dcmxx,des
Description
number
Contactor 1
dcmxx,sn
Serial Number
text
Serial number
dcmxx,brc
Board Code
text
Board code
dcmxx,stt
State
text
NONE
MISSING
PRESENT
dcmxx,typ
Shunt Type
text
NONE
LOAD
BATTERY
dcmxx,val
Reading
number
ddd.d Amps
dcmxx,sha
Shunt amp rating
number
0-9999 Amps
The shunt type defaults are as follows:
DCMC1 = Battery
DCM01 = Battery
DCM02-DCM08 = Load
DCN- Distribution Contactor Interface
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
dcnxx,ide
Identifier
number
DCN01-DCN06
dcnxx,des
Description
number
Contactor 1
dcnxx,sn
Serial Number
text
Serial number
dcnxx,brc
Board Code
text
Board code
dcnxx,stt
State
text
NONE
MISSING
OPEN
CLOSED
dcnxx,typ
Contactor interface type
text
NONE, CN1, CN2, CN3, or
CN4