Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 155
The contactor interface type defaults are as follows:
DCN01 = CN1
DCN02 = CN2
DCN03 = CN3
DCN04-DCN08 = CN4
STC- Slope Thermal Compensation
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
sc1,ide
Identifier
Text
SC1
sc1,des
Description
Text
Slope Thermal Comp
sc1,stt
State
number
0=disable 1=enable
sc1,rve
Raise Voltage Enable
number
0=disable 1=enable
sc1,fse
Probe Fail-Safe Enable
number
0=disable 1=enable
sc1,ltt
Lower Temperature Threshold
number
-5-20
°
C or 23-68
°
F
sc1,ntt
Nominal Temperature Threshold
number
15-30°C or 59-86°F
sc1,utt
Upper Temperature Threshold
number
30-55
°
C or 86-131
°
F
sc1,spt
Step Temperature
number
45-85
°
C or 113-185
°
F
sc1,lsp
Low temperature slope
number
1-10mV/
°
C per cell
sc1,usp
Upper temperature slope
number
1-10mV/
°
C per cell
INP- Input Management
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
inmnn,ide
Identifier
number
m=module
nn=input number
Examples:
IN001=input 1 on controller
IN103=inp
ut 3 on module
with ID 1
inmnn,des
Description
text
See table below
inmnn,sn
Serial Number
text
Serial number
inmnn,brc
Board Code
text
Board code
inmnn,stt
Input state
text
0=not alarming 1=alarming
inmnn,typ
Input alarm type
text
"" no alarm, for in006, this
value allows the input to
be used for either group
standby or PBT.
Polarity is ignored.
"FAN1" - drives FAN1 alarm
"FAN2"
drives FAN2
alarm
"FAJ1" – drives FAJ1 alarm
"FAJ2" – drives FAJ2 alarm
"OSA1"
drives OSA1
alarm
"AMJ1"
drives AMJ1
alarm, not valid for
NE872 or other LVD
card inputs.