Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 156
INP- Input Management
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
"AUX1" drives AUX1
alarm
"AUX2"
drives AUX2
alarm
“AUX3"
drives AUX3
alarm
“AUX4"
drives AUX4
alarm
“AUX5"
drives AUX5
alarm
“AUX6"
drives AUX6
alarm
"REMLVD" Active signal
opens battery contactors
for built-in plant input,
or for LVD inputs, it
opens the contactor on
the card where the signal
is active.
inmnn,pol
Input alarming state
text
CLOSED, OPEN
where: m is the distribution interface module ID from 1 to 4
nn is the input number from 01 to the number of inputs supported by the distribution
interface module
Built-in plant inputs
Object
Signal Name
Default Description
In001
BALM1
Fuse Alarm Major
In002
BALM2
Open String
In003
BALM3
Auxiliary 1
In004
BALM4
Auxiliary 2
In005
BALM5
Auxiliary 3
In006
BALM6
Auxiliary Major Alarm
In007
ALM1
Emergency power off
In008
ALM2
PBT/TR
In009
ALM3
Emergency power off
In010
ALM4
Auxiliary 4
In011
ALM5
Auxiliary 5
In012
ALM6
Auxiliary 6
In013
ALM7
Auxiliary 7
In014
ALM8
Auxiliary 8
In015
ALM9
Auxiliary 9
COM- Call-Out Manager
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values