Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 159
LPT -Local RS-232 Port
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
4800, 9600, 19200
lp1,dbt
Data Bits
Number
7, 8
lp1,pry
Parity
text
O, E, N
lp1,sbt
Stop Bits
Number
1, 2
lp1,tmo
Time-Out
Number
0(disabled) 45 minutes
lp1,hsh
Handshaking
text
NO, HW, SW
lp1,app
Application
Text
TERMINAL, EVENT LOG
(HW,SW)
lp1,wre
Write Enable
Number
0=disable 1=enable
(HW,SW)
ATS- Alarm Test
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
at1,des
Description
Text
Alarm Test 1
at1,stt
Alarm Test State
Number
0=inactive 1=active
at1,stg
Alarm Test Stage
text
PCR,PMJ,PMN,R1,R2,R3,R
4,R5,R6,R7
at1,lte
Alarm Test Enable
Number
0=disable 1=enable
(HW,SW)
at1,dur
Duration
Number
5-300 seconds
at1,pmj
Test Power Major
Number
0=no 1=yes
at1,pmn
Test Power Minor
Number
0=no 1=yes
at1,r1
Test Relay 1
Number
0=no 1=yes
at1,r2
Test Relay 2
Number
0=no 1=yes
at1,r3
Test Relay 3
Number
0=no 1=yes
at1,ets
Email Test
number
1=do test (sets and clears
ATA1)
at1,ems
Email Results
text
at1,bzi
Audio Test Duration
Number
5-300 seconds
at1,bzt
Audio Test State
Number
“”=Stop Test, Local=local
buzzer
at1,irt
Individual Relay Test State
Number
“”=Stop Test,
PCR,PMJ,PMN,R1,R2,R3,R
4,R5,R6,R7
Alarm Cut-off
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
aco1,des
Description
Text
Alarm Cut-off 1
aco1,stt
Alarm Cut-off State
Number
0=inactive 1=active
aco1,cst
Critical Alarm Cut-off State
Number
0=inactive 1=active
aco1,cae
Critical Alarm Cut-off Enable
Number
0=disable 1=enable
aco1,cto
Critical Alarm Cut-off Time-Out
Number
1 to 8 hours
aco1,jst
Major Alarm Cut-off State
Number
0=inactive 1=active