Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 160
Alarm Cut-off
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
aco1,jae
Major Alarm Cut-off Enable
Number
0=disable 1=enable
aco1,jto
Major Alarm Cut-off Time-Out
Number
1 to 8 hours
aco1,nst
Minor Alarm Cut-off State
Number
0=inactive 1=active
aco1,nae
Minor Alarm Cut-off Enable
Number
0=disable 1=enable
aco1,nto
Minor Alarm Cut-off Time-Out
Number
1 to 72 hours
aco1,lbe
Local Buzzer Enable
Number
0=disable 1=enable
UDE- User Defined Events
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
unnnn,des
Description
Text
30 char
unnnn,fds
Front Panel Description
text
see below
unnnn,ast
Alarm State
Number
0=inactive 1=active
unnnn,sev
Severity
Text
CRIT, MAJ, MIN, WRN,
RO
unnnn,prg
Program Line
Text
60 char
unnnn,dur
Minimum Duration
Number
> 0 seconds
unnnn,lat
Latched
Number
0=no 1=yes
unnnn,led
LED
text
BD,AC,DC,””
unnnn,acc
Contact Closure
text
R1,R2,R3,R4,R5,R6,R7,””
unnnn,dly
Notify Delay
Number
0-540 seconds
unnnn,noo
Notify On Occur
Number
0=no 1=yes
unnnn,nor
Notify On Retire
Number
0=no 1=yes
unnnn,nag
NAG On Occur
Number
0=no 1=yes
unnnn,dst
Notify Destination
text
“”, P1, P2, P3, P4, E1, E2,
E3, E4, S1, S2, S3, S4
where nnnn = 1 thru 128
DRC-Derived Channels
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
DRnn,des
Description
Text
30 char (Derived Chan nn)
DRnn,val
Value
Number
Number units
DRnn,prg
Program line
Text
60 char
DRnn,uni
Unit
Text
5 chars
Where nn is from 01 thru 8
TRS- Trend
Related
Commands
obj,attr
Description
sta
cha
ope
type
Range of Values
Obj,ide
Identifier
DCT1 for DC plant load