bye
Log-off
Syntax:
bye
Description
This command is used to terminate the session.
cha
Change Value
Syntax:
cha obj,attr=value
where: obj,attr is an object-attribute pair. For example, ps1,sid.
Description
This command is used to change system configuration parameters. Examples are listed below to
illustrate how this command works.
cha ps1,sid="My Plant"Change the site id to My Plant
cha p1,phn="123456789"Change the primary phone number to 123456789
You must be logged in as a super-
user or administrator to use this command. “” are required for
all IP addresses and associated descriptions.
cle
Clear All Latched Events
Syntax:
cle
Description
This command is used to clear latched events. These events include communication failures,
missing rectifiers, missing thermal probes, missing voltage monitoring module, distribution
fuses, and loss of redundancy alarm.
You must be logged in as a super-user to use this command.
his
Report Alarm History
Syntax:
his
Description
Syntaxhis
where: obj,attr is an object-attribute pair as defined in the following:
sum dc1,adc- report plant load current statistics
sum br1,hbt- report highest battery temperature statistics
his
Report Boost History
Syntax:
his bs1,stt
Description
This command reports the boost history in the following format:
sum bs1,stt
30-MAY-03,15:11:12,RESUMED,COMPLETED,78
30-MAY-03,12:03:34,AUTO,DISCHARGE,14
.
**