Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 166
This command is used to list all the rectifiers in the system. The command will list all present
and missing rectifiers. Missing rectifiers are rectifiers that have been removed from a shelf. The
cle will clear missing rectifiers from the controller's memory and they will no longer be listed
by this command. Return value for a system with 3 rectifiers on shelf 1 would look like the
following:
* lis rec
G11
G12
G13
.
* _
login
Log-in
Syntax:
login “password
where password is either the user, super-user or administrator password
Description
This command is used to log-in as a user, super-user or administrator. For example, if you are
currently logged into the controller as a user but would like to change the site id you must first
use this command to log-in as a super-user. You must be logged in as an administrator in order
to upgrade the software and change passwords.
ope
Operate a Control
Syntax:
ope
obj,attr=value
where: obj,attr is an object-attribute pair. For example, dc1,pbt.
Description
This command is used to operate a system control parameter. Examples are listed below to
illustrate how this command works.
ope ps1,usl=1Update serial link
ope dc1,stt="boost"Place plant into boost mode
You must be logged in as a super-user to use this command.
pas
Change Passwords
Syntax:
pas t,“password”,“password”
where “t” is to change the user password, “s” to change the super-user password,
and “a” to change the administrator password. password is the new password
Description
This command changes either the user or super-user password. You must be logged in as a
super-user to use this command. The password is sent twice in order to avoid mistakes. The
password must have at least 6 characters but no more than 15 characters.
You must be logged in as a super-user to use this command.
sta
Report Status
Syntax:
sta obj,attr
where: obj,attr is an object-attribute pair. For example, ps1,sid.