Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 183
Factory Default
Factory 24V
Rectifier Default
Factory 48V
Rectifier
Default
Category Description Range Factory Factory 24V Factory 48V obj,attr
Daylight Saving End
mon:wk:dow:min
mon:-1:dom:min
"11:1:0:120" PS1,DSE
Time zone offset
-840 - +840
minutes (±14
hours)
0 PS1,TZO
Uninstall Equipment Timeout 0 to 60s 15 PS1,UET
Critical Equals Major
1=Enabled
0=Disabled
1 PS1,CEM
User Password "lineage" PAS U,
Super-user Password "super-user" PAS S,
Administrator Password "administrator" PAS A,
Low Voltage Disconnects
Battery Disconnect 1
Battery Disconnect Control Mode
0=none,
1=voltage
2=voltage/time,
3=adaptive
1 CN1,DAM
Battery Disconnect Time Delay 0:0:0 to 4:59:59 0:00:00 CN1,DDY
Battery Reconnect Control Mode
0=none,
1=voltage
2=voltage/time
1 CN1,RAM
Battery Reconnect Time Delay 0 to 300 sec 0 CN1,RDY
Battery Disconnect Description <=32 Chars "LVBD" CN1,DES
Battery Disconnect Open
Description
<=32 Chars "LVBD Open"
CNO1,DES
Battery Disconnect Open Front
Panel Description
<=32 Chars "LVBD Open" CNO1,FDS
Battery Disconnect Failed
Description
<=32 Chars "LVBD Failed" CNF1,DES
Battery Disconnect Failed Front
Panel Description
<=32 Chars "LVBD Failed"
CNF1,FDS
Load Disconnect 1
Load 1 Disconnect
1=Enabled
0=Disabled
0 CN2,ENA
Load 1 Disconnect Control Mode
0=none,
1=voltage
2=voltage/time
1 CN2,DAM
Load 1 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.50 43.00 CN2,DTH
Load 1 Disconnect Time Delay 0:0:0 to 4:59:59 0:00:00 CN2,DDY
Load 1 Reconnect Control Mode
0=none,
1=voltage
2=voltage/time
1 CN2,RAM
Load 1 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00 44.00 CN2,RTH
Load 1 Reconnect Time Delay 0 to 300 sec 0 CN2,RDY
Load 1 Disconnect Description <=32 Chars "LVLD1" CN2,DES
Load 1 Disconnect Open
Description
<=32 Chars "LVLD1 Open" CNO2,DES
Load 1 Disconnect Open Front Panel
Description
<=32 Chars "LVLD1 Open" CNO2,FDS
Load 1 Disconnect Failed
Description
<=32 Chars "LVLD1 Failed" CNF2,DES
Load 1 Disconnect Failed Front
Panel Description
<=32 Chars "LVLD1 Failed" CNF2,FDS
Load Disconnect 2
LV Load 2 Disconnect
1=Enabled
0=Disabled
0 CN3,ENA
LV Load 2 Disconnect Control
Mode
0=none,
1=voltage
2=voltage/time
1 CN3,DAM
LV Load 2 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00 42.00 CN3,DTH
LV Load 2 Disconnect Time Delay 0:0:0 to 4:59:59 0:00:00 CN3,DDY
LV Load 2 Reconnect Control Mode
0=none,
1=voltage
2=voltage/time
1 CN3,RAM