Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 185
Factory Default
Factory 24V
Rectifier Default
Factory 48V
Rectifier
Default
Category Description Range Factory Factory 24V Factory 48V obj,attr
Group Standby/Sequencing Enable
1=Enabled
0=Disabled
0 DC1,RSQ
Remote rectifier Off Enable
1=Enabled
0=Disabled
1 PS1,RRF
Rectifier Redundancy Threshold 1 to 80 1 RLS1,THR
Multiple Rectifier Fail 2 to 88 2 MFA1,THR
Oring FET test enable
1=Enabled
0=Disabled
1 GM1,OFT
Efficiency Enable
1=Enabled
0=Disabled
0 DC1,EME
Efficiency Target 20% to 95% 70 DC1,EMT
Efficiency Rectifier Turn On
Threshold
25% to 100% 76 DC1,EMO
Efficiency initial delay
1 to 30 minutes
10 DC1,EMI
Efficiency Inter-Rectifier delay 1 to 30 minutes
10 DC1,EMW
Walk-In Enable
1=Enabled
0=Disabled
1
GM1,WIE
Converter Current Limit 30 to 100% 100 CP1,CLM
Converters
Converter Redundancy Loss Enable
1=Enabled
0=Disabled
1 CP1,RME
Remote converter Off Enable
1=Enabled
0=Disabled
0 CP1,ROF
Low Voltage Disconnect Input
Threshold
20.0 to 25.0V
40.0 to 50.0V
23.0 46.0 CP1,DTH
Low Voltage Reconnect Input
Threshold
22.0 to 27.0V
44.0 to 54.0V
25.0 50.0 CP1,RTH
Low Voltage Disconnect Enable
1=Enabled
0=Disabled
0 CP1,LVD
Converter Redundancy Threshold 1 to 32 1 CRL1,THR
Multiple Converter Fail 2 to 8 2 CMFA1,THR
Battery
Discharge Test
Timed Test Duration 0:0:0 to 23:59:59 2:00:00 BR1,TMD
Automatic Battery Test Feature
disabled, 20%,
timed, Ah Out
"disabled" BR1,BTE
Automatic Test (AT) Interval 1 to 18 Months 12 BR1,TIN
Date For Next Automatic Test yyyy-mm-dd 1/1/2099 BR1,ATD
Start Time For Automatic Test 0 to 23 0 BR1,ATH
Hours To Wait From Last BD
Before AT
0 to 240 hours 72 BR1,ATW
Manual Test Type
disabled, 20%,
timed, Ah Out
"20%" BR1,MTT
Battery test Ah to be removed 10-1000Ah 10 BR1,AHO
Reserve Time Low (Full Capacity) 00:00 to 99:59 00:00 RTL1,THR
Real-time Reserve Low (During
BD)
00:00 to 99:59 00:00 RRTL1,THR
Battery Boost
Boost Maximum Duration 1 to 80 Hours 1 BS1,TMD
Automatic Boost Feature
disabled, timed,
or current
"disabled" BS1,ATM
Auto Boost BD Multiplication
Factor
0.1 to 9.0 0.5 BS1,AMF
Auto Boost Termination Current
Threshold
1 to 999A 5 BS1,CTA
Shunt Monitors
Plant Shunt Type
Battery/None
/Load
"BATTERY" DCMC1,TYP
Plant Shunt Current Rating 0 to 9999 Amps 100 DCMC1,SHA
ID1 Type
Battery/None
/Load
"BATTERY" DCM01,TYP