SEVERITY RELAY USER RELAYS
LED SNMP
Description CRIT PMJ PMN WRN RO R1 R2 R3 R4 ALM DST
Object
ID
Auxiliary 12
MAJ
AUX12
Auxiliary Major
MAJ
AMJ1
Battery Test Active
RO
BTA1
Battery on Discharge (Float and Boost)
MAJ R1 ALM
BDA1
Battery Voltage (Cell) Imbalance
Detect
MIN
SCD1
Check Battery/Battery Test Failed
MIN
BFA1
Clock Changed
RO
CLC1
Configuration Changed
RO
CCH1
Controller Fail (Not user mappable)
x x x
Converter Distribution Fuse
MAJ R4
CDFA1
Converter Fail
MAJ R2
CFA1
Converter Fan Fail
MIN R2
CFN1
Converter Input Fail
MIN
CIN1
Converter Low Voltage
CRIT
CVLA1
Converter High Voltage Major
MAJ
CHVA1
Converter High Voltage Minor
MIN
CHFV1
Converter ID Conflict
MAJ
CDID1
Converter Redundancy Loss
MAJ R2
CRL1
Emergency Power Off
MAJ
EPO1
Energy Management Disabled
WRN
EMD1
Excessive Login Attempts
WRN
EXL1
External Password Reset
WRN
EPR1
Fuse Major
MAJ R4
FAJ1
Fuse Minor
MIN
FAN1
High Ambient Temperature
MIN
AMTH1
High Battery Temperature
MIN
BTHA1
High Voltage
MIN
HFV1
History Cleared
RO
HCL1
ID Conflict
MAJ
DID1
ID Not Configured
MAJ
ZID1
Imminent Low V Shutdown
MAJ
ISD1
Incompatible Converter
MIN
ICC1
Incompatible Rectifier
MIN R2
ICR1
Load Share Fail
MIN
LSF1
Low Ambient Temperature
MIN
AMTL1
Low Battery Temperature
MIN
BTLA1
LVBD Failed
MAJ
CNF1
LVBD Open
MAJ
CNO1
LVLD 1 Failed
MAJ
CNF2
LVLD 1 Open
MAJ
CNO2
LVLD 2 Failed
MAJ
CNF3
LVLD 2 Open
MAJ
CNO3
LVLD 3 Failed
MAJ
CNF4
LVLD 3 Open
MAJ
CNO4