Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 21
System Inputs/Outputs-Continued
Plant Current Measurement
Accuracy
0 to +50°C
-40 to +85°C
Resolution
±0.5% of full scale
±1.25% of full scale
1A
Temperature Measurement Accuracy
One-Wire Serial probes
-5 to +55°C
-40 to +85°C
Resolution
±1°C
±3°C
0.1°C
Environmental
General Specification
Operating Temperature Range -40 to 75°C (-40 to 167°F)
Storage Temperature Range -40 to 85°C (-40 to 185°F)
Altitude
-200 to 13,000 feet (-61 to 3962 meters) See Note 1
Humidity
10% to 95% non-condensing
Audible Noise
< 60 dBA
Earthquake Rating
Zone 4, upper floors
Safety / Standards Compliance
Item Specification
Safety Agency Approvals
Underwriters Laboratories (UL) Listed per Subject
Letter 1801: Power Distributi
on Center for
Communications Equipment, and cUL Certified (CSA
22.2 950): Safety of Information Technology
Equipment
European Economic Community (EEC)
Directives
EMC Directive 89/336/EEC, Low Voltage Directive
73/23/EEC as amended by Marking Directive
93/68/EEC
Radiated and Conducted Emissions FCC Part 15, Class A
EN55022 (CISPR22), Class A
Electromagnetic Immunity Meets Telcordia GR-1089-CORE
Electrostatic Discharge EN61000-4-2 Level 1-4
RF Immunity IEC61000-4-3 Level 3, 10 V/m
Conducted Immunity IEC 61000-4-6 Level 3, Input Power Ports
IEC 61000-4-6 Level 2, Telecom Ports
Voltage Dips, Interruptions, and Variations IEC 61000-4-11, EN55024 (CISPR24)
Note 1: For altitudes above 5000 feet (1524 meters), derate the temperature by 3.6 °F per 1000 feet