LVLD3 (Disabled)
Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None
Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V
Time Delay (0 min); Range: 0-300min
Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None
Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V
Time Delay (0 sec); Range: 0-300sec
System-Date/Time/Temperature Configurations
Items in this web page are used to define the different parameters associated with the controller’s
date, time, and temperature units and formats.
Date and Date
Format
Sets system date and format. The format for date can be selected from:
mm/dd/yyyy, dd/mm/yyyy, yyyy/mm/dd, mm-dd-yyyy, yyyy-mm-dd,
dd-mm-yyyy, mm/dd/yy, yy/mm/dd, dd/mm/yy, mm-dd-yy, yy-mm-
dd, or dd-mm-yy and the format for time can be 12HR/24HR format.
The factory default is Date: mm/dd/yyyy
Time and Time
Format
Sets system date and format. The format for date can be selected from:
mm/dd/yyyy, dd/mm/yyyy, yyyy/mm/dd, mm-dd-yyyy, yyyy-mm-dd,
dd-mm-yyyy, mm/dd/yy, yy/mm/dd, dd/mm/yy, mm-dd-yy, yy-mm-
dd, or dd-mm-yy and the format for time can be 12HR/24HR format.
The factory default is Time: 12HR.
Use PC Date and
Time
When selected, the controller will update its date and time to the
connected users PC.
Network Time
Server
When configured with a non-zero (“0.0.0.0”) IP address the controller
will automatically at 12:00AM each day connect to the given Network
Time Server address and update its time and date using the configured
Time Zone Offset. Note: when the NTP address is set it is necessary to
reboot the controller for the feature to operate.
The factory default IP is “0.0.0.0” which is disables the feature.
Time Zone Offset
Time offset from GMT. The range for this offset is between -14:00