Owner's manual

Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011 9
Management of four independent Low Voltage Disconnects (LVDs)
Up to eight contactors assignable to the LVDs
Load disconnects operated by low voltage, low voltage and/or time delay,
remote command, or external control signal
Battery disconnect operated by voltage threshold, voltage threshold and/or time,
Adaptive Threshold, remote command, high battery temperature, or Emergency
Power Off (EPO) signal
Integrated contactor control for single contactor, additional contactor control through
remote distribution and control modules
Battery recharge current limit feature
Low and high temperature voltage compensation
Individual adjustable slopes
High temperature step function
Probe Fail-Safe feature
Manual and automatic Boost
Local (manual) discharge test, remote discharge test, and periodic discharge test
capability.
Reserve time calculations with configurable threshold
Manual time threshold for pass/fail criteria
1-Wire monitoring
Up to six ES771 Mid-string voltage monitors (Configurable mid-string
imbalance voltage threshold alarm)
Up to sixteen QS873 battery thermal probes (Configurable High, Very High,
Low, and Very Low battery temperature alarms)
Alarm management of DC distribution
Six configurable system alarm inputs
Additional Factory configurable Input/Output options:
Up to 9 configurable binary alarm inputs or
Up to six alarm outputs or