User guide

14 Design and specifications are subject to change without notice S47183e rev.03 2010-06-07
Control box terminals
1x12-pole AC 400 V, 20 A
4x15-pole AC 250 V, 8 A
Closing solenoid drive
1)
Rated voltage AC 48 V - 230 V and DC 48 V - 220 V
Operating range 80 % - 115 % of rated voltage
Power consumption Gerapid 2607 / 4207 1750 W / 2000 W
Power consumption Gerapid 6007 / 8007 2600 W / 2600 W
Minimal CLOSING command duration 100 ms
min.interval between two "CLOSE" operations ~8 s w/o NEKO installed; ~14 s with NEKO
Internal voltage converter
1)
Input: Voltage range DC 33 - 85 V
for Gerapid 2607, 4207, 6007, 8007
Output: Voltage range DC 24 V (±5%)
Current 6 A permanent
Model description PCMD 150 48 S24W-GE
Input: Voltage range DC 88 - 145 V
Output: Voltage range DC 24 V (±5%)
Current 6 A permanent
Model description PCMD 150 110 S24W-GE
Input: Voltage range AC 115 - 240 V, DC 125 - 353 V
Output: Voltage range DC 24 V (±5%)
Current 3 A permanent, 5 A/100 ms
Model description PCMA 70 S24W-GE
External power supply
with plug and socket unit requires extrnal 24 V (±5%) DC
Aux. contact HS 1…HS 10,
Rated operational voltage Ue/AC 230 V
OC trip target (code 10)
Rated operational current Ie/AC-15 1 A
Arc chutes indicator (code 17)
Conventional thermal current Ie/AC-12 (Ith) 10 A
Rated operational voltage Ue/DC 110 V / 220 V
Rated operational current Ie/DC-13 0.5 A / 0.3 A
Minimum current/voltage ratings 0,1 mA / 6 V DC
Contact duty (min. value) DC 10 V / 2 mA
Shunt trip standard
Rated voltage/power Uc/Pc 24 V / 100 W
Operating range: OFF 21.6 V - 26.4 V
Shunt trip double winded
Rated voltage/power Uc DC 110 V/ DC 125 V/ DC 220 V
Rated power for a single winding Pc 230 W
UVR
Rated voltage Uc 24 V
(Zero voltage release) Operating range: OFF < 4 V
Operating range: ON 24 V (±10%)
Power consumption ~ 10 W
ED impulse release
Energie source: Capacity 2000 µF
Charging voltage 300 V
Switching interval max. 2/min with 10 consecutive operations
Endurance 1 000 operations with 1 operation per 180 s
Firing signal level / duration
6 - 24 V / 100 - 1000 ms
Charging signalization relay AC duty : AC 250 V/ 0.5 A - AC 120 V /1 A
DC duty : DC 220V/0.1A - DC 125V/0.3A - DC 10V/3A
1)
Standard ambient conditions acc. to EN 50123-1 Attachement B. For meeting outside of this standard range, please call back.
Table 2a: Technical data of auxiliary circuits
Components Technical datas of control circuits
Us / In
SU-Control
CLOSE-push-button -S1 DC 24 V / approx. 10 mA
ST releasing
push-button-S2 DC 24 V / approx. 4 A
UVR releasing
push-button -S2 ( -X2 :6 / :7) DC 24 V / approx. 10 mA
push-button -S2 ( -X2 :8 / :9 ) DC 24 V / approx. 450 mA
ED-coil tripping w/o NEKO
push-button -S3 DC 300 V / 750 A / 3 ms
ED-coil tripping with NEKO
Connect "Firing signal" at ( -X2 :10 / :11 ) DC 6 V…24 V / approx.20 mA
Table 2b: Control circuits ( directional values to rate the components )