User guide

2010-06-07 S47183e rev.03 Design and specifications are subject to change without notice 17
4.3 Electrical diagrams
4.3.1 Wiring code
The main circuits are not shown in the wiring diagrams
for transparency. The control circuit is presented as a
typical circuit diagram and is a combination of numbered
basic diagrams for drives, trips and indicators.
Using the key numbers of the basic plan, you can derive
the number of the complete diagram.
WARNING: Some non standard electrical circuits do not
comply with the diagrams in this instruction. Such circuits
are coded with unique numbers i.e 36/0033. In such a
case an appendix to this instruction is delivered, which
contains relevant electrical diagrams.
Coding positions:
Key position:
1 / 2 3 4 5 6 7 8
Breaker type
Aux. voltage supply
ED impulse release
Closing drive
Aux. tripping device
Indicators
Aux. switches
SEL system
EXAMPLE:
Key number:
36 / 1 0 20 20 01 1
Gerapid
With voltage converter
Without ED and NEKO
With closing drive
With UVR release
With OCT trip target
With 3 aux. switches
Without SEL system
Fig. 22 Example code shown on the nameplate.
Key
position
Key
number
Designation
Type
1 36 Gerapid
Auxiliary voltage
2 1 Voltage converter
2 DC 24 V external supply
Tripping coil
3 0 Without ed-trip coil
1 With ed-trip coil
2 With ed-trip coil and NEKO
control unit
Drive
4 20 Solenoid drive with
SU control unit
Tripping device
5 00 Without trip unit
10 With shunt trip
20 With zero voltage release
Indication device
6 00 Without indicators
01 OCT trip target
02 Arc chute indicator
03 OCT + arc chute indicator
Auxiliary contacts
7 1 3 auxiliary contacts
2 5 auxiliary contacts
3 10 auxiliary contacts
Current-measurement system
8 S with SEL
Indication of components
Q1 Impulse ED coil
Q2 Closing drive coil
S1 Push button „CLOSE“
S2 Push button „OPEN“, type NO
S3 Push button “OPEN”, type NC
SU control PCB:
K1 Closing relay
K2 Internal closing stop relay
1)
Shunt trip, zero voltage release PCB:
K1 Internal closing stop relay
1)
K2 Tripping relay
HS11 Shunt trip self cut-off auxiliary contact
ED-tripping device with internal NEKO PCB:
K1 Voltage monitoring relay
K2
Internal closing stop relay
1)
1) These relays are part of internal closing stop circuit.
It is a 24 V DC closed circuit, through all PCBs in the box,
except SEL. Serial connection of all relays is realized
through connections ( :5/:6) in each PCB. This circuit
provides priority of a tripping signal over a closing signal.
Additionally it prevents from closing the internal supply
24 V DC lost at UVR PCB or NEKO PCB.