Owner manual

Infinity D Power System Installation Guide: -48V Plants H2007001
Issue 2.0, June 3, 2009 19
UL Ratings as reflected in the UL Report in May 2009. Please note the available rectifier
output is reduced from the nameplate rating when converters are introduced to the system.
ELECTRICAL RATING:
Input (ac) Output (dc)
Model
J2008001
Battery
Panel
V (50/60Hz) Current Vdc (++) Max Current(+++) Max Power
L001, L002,
L005, or
L006
640A charge
800A discharge
17,500 W
H2007001
Type A(+)
L003, L004,
L007, or
L008
200-240
(up to 28
feeds)
15 A draw 22 – 29
1280A charge
1600A discharge
34,985 W
Primary:
22 – 29
Primary:
640A charge
800A discharge
L001, L002,
L005, or
L006
200-240
(up to 28
feeds)
15 A draw
Secondary:
48 – 54.5
Secondary:
120A
17,500 W
maximum
combined
output
Primary:
22 – 29
Primary:
1280A charge
1600A discharge
H2007001
Type B(+)
L003, L004,
L007, or
L008
200-240
(up to 28
feeds)
15 A draw
Secondary:
48 – 54.5
Secondary:
120A
34,985 W
maximum
combined
output
L001, L002,
L005, or
L006
640A charge
800A discharge
34,880 W
H2007001
Type C(+)
L003, L004,
L007, or
L008
200-240
(up to 28
feeds)
15 A draw 44 – 57
1280A charge
1600A discharge
69,760 W
Primary:
44 – 57
Primary:
640A charge
800A discharge
L001, L002,
L005, or
L006
200-240
(up to 28
feeds)
15 A draw
Secondary:
24–27.25
Secondary:
300A
34,880 W
maximum
combined
output
Primary:
44 – 57
Primary:
1280A charge
1600A discharge
H2007001
Type D(+)
L003, L004,
L007, or
L008
200-240
(up to 28
feeds)
15 A draw
Secondary:
24–27.25
Secondary:
300A
69,760 W
maximum
combined
output
(+) May be followed by –SD. When followed by –SD, the AC input will be up to 16 or 8 feeds rated:
(16)x 15 amps each feed or (8)x 30 amps each feed.
(++) The marked output voltage may be any voltage range or specified voltage as long as it is within
the range specified in the electrical rating table.
(+++) Maximum 45°C ambient for output rating not exceeding 960A charge and 1200A discharge.
Otherwise, 40°C ambient. The secondary (converter) input is a load for the primary (rectifier)
output. This must be considered when loading the plant to its maximum rated primary output.