Infinity D Power System Installation Guide: -48V Plants H2007001
Issue 2.0, June 3, 2009 20
DC DISTRIBUTION PANEL OVERCURRENT-PROTECTION DEVICE
CONFIGURATIONS
Circuit Breakers
Shelf(+)
Maximum
Amps(++),(+++)
Manufacturer Series Rating(+++++)
Comments
Airpax
LMLK,
LMLHPK
3-70A 1-pole
100A 2-pole
150A 2-pole
250A 3-pole
Cumulative adjacent
circuit breaker ratings
cannot exceed 250A.
QSGMT6
6 fuse holders –
57.6A total; 15A
rated fuse/position
R/C (QPQY2/8); uses
R/C fuse (JDYX2) by
SOC, Type AX1 or
AX1-B
J2007002
400 charge
500 discharge
Lineage Power
J2007002
L005
(++++)
3-70A 1-pole
100A 2-pole
Cumulative circuit
breaker ratings cannot
exceed 200A.
(+) - Includes all List options.
(++) - Maximum amps that the distribution section of the shelf is rated. Power supply output may be
rated less.
(+++) - Plant ratings that exceed 640A charge and 800A discharge: top shelf adjacent to battery panel
shall not exceed 336A charge and 400A discharge.
(++++) - The J2007002 L051 shelf option is ten additional bullet-breaker positions located on right side
of shelf.
(+++++) - Plant ratings that exceed 640A charge and 800A discharge: top shelf adjacent to battery panel
shall not use either a 150A 2-pole or 250A 3-pole circuit breaker.
POWER SUPPLIES ALLOWED
IN H2007001 POWER DISTRIBUTION CENTER
Power Supply Model(#) Type Manufacturer Certification
NE075AC24 rectifier
NE030DC48 converter
NE100AC24 rectifier
NE050AC48 rectifier
NE075DC24 converter
Lineage Power
R/C (QQGQ2/QQGQ8)
(#) - May be provided with a non-safety affecting suffix.