Table 45 Specifications
General Specifications
Item
Specification
Input Voltage Ranges (power)
+/-24 volts: from +/-18 volts to +/-30 volts;
-48 volts: from -36.5 volts to -60 volts SELV
Input Power 6.0 watts maximum
Input Power Connections
NE843A/CP843A/EP843D, No external connection required;
NE843C/NE843E/NE843G/NE843P, (J9)12-pin connector
Bonding Network
Suitable for installation as part of either
Common Bonding Network (CBN)
an Isolated Bonding Network (IBN)
Facilities
Suitable for installation in
Network Telecommunication Facilities
Locations where the NEC applies
DC Return
Isolated DC Return (DC-I) or
Common DC Return (DC-C)
Front Panel User Interface
4 or 8-line by 40-character LCD
Severity sensitive backlit LCD
(LEDs on NE 843P);
Three status LEDs (20 on NE843P)
Voltage test jacks;
Six Push Buttons
(Rotary Control + 2 Push Buttons on NE843P)
System Configuration Methods
Front panel LCD display and menu keys
(J5) and (J8) 10/100 Base-T port/s
(J7) DB9 for RS-232 port: T1.317 or EasyView
(J6) RJ11 for phone line connection MODEM option
Maximum Power Units
60 NE Power Units
32 CP Power Units
Low-Voltage Disconnects
Manage up to eight LVD contactors using up to 3 independent
configurable Load disconnect thresholds (LVLDs) and 1 configurable
Battery disconnect threshold (LVBD).
Temperature Monitoring
Up to 16 One-Wire Battery Temperatures;
One on-board internal ambient temperature